Datasheet
New Energy labeling for air conditioners
Under the new labeling the energy efficiency of air conditioning systems will be calculated based on seasonal
performance.
Climate zones for calculating Heating (SCOP),for Heating mode a comprehensive temperature profile for the whole of
Europe could not be created, for this reason the EU is divided into three climate zones, this ensures the energy efficiency
calculation applies the actual regional ambient temperatures.
• Warmer – annual temperature of Athens
• Average – annual temperature of Strasbourg
• Colder – annual temperature of Helsinki
Energy Efficiency Class SEER SCOP
A+++ SEER ≥ 8,50 SEER ≥ 5,10
A++ 6,10 ≤ SEER < 8,50 4,60 ≤ SEER < 5,10
A+ 5,60 ≤ SEER < 6,10 4,00 ≤ SEER < 4,60
A 5,10 ≤ SEER < 5,60 3,40 ≤ SEER < 4,00
B 4,60 ≤ SEER < 5,10 3,10 ≤ SEER < 3,40
C 4,10 ≤ SEER < 4,60 2,80 ≤ SEER < 3,10
D 3,60 ≤ SEER < 4,10 2,50 ≤ SEER < 2,80
WARMER (ATHENS)
Temperatures Conditions
Partial
Load
Outdoors Indoors
DB WB DB
- - - 20
O
C
100% 2
O
C 1
O
C 20
O
C
64% 7
O
C 6
O
C 20
O
C
29% 12
O
C 11
O
C 20
O
C
AVERAGE (STRASBOURG)
Temperatures Conditions
Partial
Load
Outdoors Indoors
DB WB DB
88% -2
O
C - 2
O
C 20
O
C
54% 2
O
C 1
O
C 20
O
C
35% 7
O
C 6
O
C 20
O
C
15% 12
O
C 11
O
C 20
O
C
COLDER (HELSINKI)
Temperatures Conditions
Partial
Load
Outdoors Indoors
DB WB DB
61% -7
O
C - 8
O
C 20
O
C
37% 2
O
C 1
O
C 20
O
C
24% 7
O
C 6
O
C 20
O
C
11% 12
O
C 11
O
C 20
O
C
Climate zones for calculating Cooling (SEER), only ONE climate zone for calculating Cooling efficiencies.The climate data
for Strasbourg is the single reference point for the whole of Europe.
SEER
Temperatures Conditions
Partial
Load
Outdoors Indoors
DB DB WB
21% 20
O
C 27
O
C 19
O
C
47% 25
O
C 27
O
C 19
O
C
74% 30
O
C 27
O
C 19
O
C
100% 35
O
C 27
O
C 19
O
C