DOCUMENT: NBZ0002 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE TX SERIES Low Voltage Digital Solid State Starter 48 - 1250 A Issued: 11/04 Manufactured in the USA
SAFETY IMPORTANT MESSAGES Read this manual and follow its intructions. Signal words such as DANGER, WARNING and CAUTION will be followed by important safety information that must be carefully reviewed. DANGER Indicates a situation which will result in death, serious injury, and severe property damage if you do not follow instructions. WARNING Means that you might be seriously injured or killed if you do not follow instructions. Severe property damage might also occur.
SAFETY SAFETY CODES Toshiba motor control is designed and built in accordance with the latest applicable provisions of NEMA and the National Electrical Code. Installations must comply with all applicable state and local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions provided in this manual. HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and property damage. • Turn off and lock out Primary and Control Circuit Power before servicing.
TX TX Series Series Digital Solid State Soft Starter 48 - 1250A Installation & Operation Manual Chapter 1: Introduction ...................................................................................................... 1 48 - 1250A 1.1 1.2 1.3 1.4 1.5 General Specifications Theory of Operation General Protection Thermal Overload Protection Chapter 2: Installation ....................................................................................................... 8 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.
TX Series 48 - 1250A TOSHIBA - 96
TX Series 48 - 1250A Chapter 1 - Introduction This chapter is a brief introduction to the TX Series soft starter and describes product operation and unit features. 1.1 - General The TX Series is a high-end digitally programmable solid state reduced voltage soft starter. This heavy duty starter provides reduced voltage, stepless soft starting of 3-phase AC induction motors, protecting mechanical components from excessive torque stress and electrical systems from the effects of high motor inrush currents.
TX Series 48 - 1250A 1.2 Specifications (continued) Advanced Motor Protection Two Stage Electronic Overload Curves Starting: programmable for Class 5 - 30 or locked rotor time. Run: Programmable for Class 5 - 30 when "At-Speed" is detected. Overload Reset Manual (default) or automatic Retentive Thermal Memory Overload circuit retains thermal condition of the motor regardless of control power status. Unit uses real time clock to adjust for off time.
TX Series 48 - 1250A 1.
TX Series 48 - 1250A 1.3 - Theory of Operation The power of the TX Series is in the CPU, a microprocessor based protection and control system for the motor and starter assembly. The CPU uses Phase Angle Firing of the SCRs to apply a reduced voltage to the motor, and then slowly and gently increases torque through control of the voltage and current until the motor accelerates to full speed.
TX Series 48 - 1250A Other starting methods available in the TX Series are: · Current Ramp: uses a closed current feedback PID loop to provide a linear torque increase up to a Maximum Current level. · Constant Current: current is immediately increased to the Current Limit point and held there until the motor reaches full speed. · Custom Curve: gives the user the ability to plot torque and time points on a graph. The soft starter will then accelerate the motor following these points.
TX Series 48 - 1250A Run Mode: The soft starter enters the Run Mode when it reaches full output voltage and the motor current drops below the FLA setting (motor nameplate FLA plus service factor) for a predetermined period of time.
TX Series 48 - 1250A Run Mode overload protection is initiated when the TX Series determines that the motor is At-Speed. Overload Protection is initiated when the motor RMS current rises above a “pick-up point” (as determined by the motor nameplate FLA and service factor). Run mode protection is provided by the CPU monitoring the Dynamic Thermal Register. Data for the Dynamic Thermal Register is accumulated from I2t calculations and cooling rates.
TX Series 48 - 1250A Chapter 2 - Installation 2.1 Receiving and Unpacking Upon receipt of the unit: • Carefully unpack the unit and inspect it for any shipping damage. Report any damage immediately and file a claim with the freight carrier within 15 days of receipt. • Verify that the model number on your unit matches your purchase order. • Confirm that the ratings label on the unit matches or is greater than the motor’s HP and current rating. 2.
TX Series 48 - 1250A Remove all sources of power before cleaning the unit! WARNING In dirty or contaminated atmospheres the unit should be cleaned on a regular basis to ensure proper cooling. Do not use any chemicals to clean the unit. To remove surface dust use 80 to 100 psi, clean, dry compressed air only. A three inch, high quality, dry paint brush is helpful to loosen up the dust prior to using compressed air on the unit. 2.
TX Series 48 - 1250A 2.7 Power Connections Connect appropriate power lines to the unit input terminals marked L1, L2, L3. Avoid routing power wires near the control board. Connect the motor leads to the unit terminals marked T1, T2, T3. Refer to NEC standards for wire length and sizing. Never interchange input and output connections to the unit. This could cause excessive voltage in the control logic circuit and may damage the unit.
TX Series 48 - 1250A 2.8.2 Two-Wire Connection An alternate connection for unattended operation replaces start/stop push buttons by connecting a maintained contact closure between pins 3 and 5 on TB4. When the maintained contact is used for start/stop it is necessary to set the overload setpoint to the manual reset position. This will prevent the motor from restarting if the thermal overload trips and then cools off.
TX Series 48 - 1250A 2.8.4 Power Board 2.8.
TX Series 48 - 1250A 2.9 CPU Board Connections There are eight digital inputs on the CPU board. Four of the inputs are user programmable. There are also two analog outputs, a tachometer feedback input. 20 20 1 2 + - 3 4 5 + - 6 7 8 + - 1 2 3 4 + - 5 6 7 8 Note: Install program jumper to enable setpoint programming. Jumper must be removed after programming or for prolonged storage to preserve settings.
TX Series 48 - 1250A 2.10 Communications Board Full (RS422) or half (RS485) duplex Modbus communications port is available at TB1 on the communications board. No field wiring connections are required for TB2. REAR VIEW (RS485) (RS422) Note: Remove for last unit in modbus string 2.10.
TX Series 48 - 1250A 2.
TX Series 48 - 1250A Chapter 3 - Start-up WARNING THE TX UNIT DEALS WITH POTENTIALLY LETHAL VOLTAGE LEVELS. YOU MUST BE CERTAIN THAT PERSONNEL ARE THOROUGHLY TRAINED IN THE APPLICABLE SAFETY PRECAUTIONS BEFORE PROCEEDING WITH THIS SECTION! 3.1 Preliminary Start-Up Check List Please make the following checks before applying power to the unit: • Supply voltage matches the rated supply voltage of the unit. • Horsepower and current ratings of the motor and unit match or the unit has a higher rating.
TX Series 48 - 1250A The current limit must be set high enough to allow the motor to reach full speed. The factory setting of 350% is a good starting point. Do not set the current limit too low on variable starting loads. This could cause the motor to stall and eventually cause the overload protection to trip. 3.4 Deceleration Adjustments (Pump Control) Decel extends the stopping time on loads that would otherwise stop too quickly if allowed to coast to stop.
TX Series 48 - 1250A Another common application for decel control is on material handling conveyors as a means to prevent sudden stops that may cause products to fall over or to bump into one another. In overhead crane applications, soft stopping of the Bridge or Trolley can prevent loads from beginning to over swing on sudden stops. 3.4.
TX Series 48 - 1250A 3.5 Sequence of Normal Operation • • • • • • Apply control power and check that the “Power” LED comes on. (Display 1) Apply three phase power to the unit. The motor should run only when the start command is applied. Apply the start command. (Display 2). The RUN LED will be lit. (Display 3) The AUX3 LEDs will be lit. If the motor does not enter run mode in the set time, a trip will occur. The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has energized.
TX Series 48 - 1250A Chapter 4 - User Interface & Menu Navigation This chapter explains the keypad operator interface, the LCD descriptions and the programming features 4.1 Keypad/Operator Interface The TX Series user keypad/keypad operator interface consists of: • 2 row by 20 characters Liquid Crystal Display (LCD) • 12 LEDs • 8 pushbuttons Note: The TX Series is menu driven and there are three levels of programming. The programming for two of these levels is password protected.
TX Series 48 - 1250A 4.2 Menu Navigation MENU (1) PAGE 1 BASIC CONFIGURATION Notes: 1. The MENU keys allow you to toggle the screens between the Setpoint Menu and the Metering Menu. Simply use the arrow keys to get to the different screens within each menu. Example: To access Setpoint Page 3: PHASE & GROUND SETTINGS, press the MENU key once and the DOWN ARROW two times. 2. Levels 1, 2 and 3 indicate password protection levels for these setpoint pages.
TX Series 48 - 1250A 4.2.1 Password Access Screens in Level 1 of the setpoint menu can be changed without password access because they list basic motor information. Screens in Levels 2 and 3 require passwords because they provide more in-depth protection and control of the TX Series unit. The password in Levels 2 and 3 can be changed by the user. NOTE: Setpoints can only be changed when the motor is in Stop/ Ready Mode! The TX will not allow a start if it is still in the Edit Mode.
TX Series 48 - 1250A Chapter 5 - Setpoint Programming The TX Series has twelve programmable setpoint pages which define the motor data, ramp curves, protection, I/O configuration and communications. In Section 5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages are illustrated and defined for easy navigation and programming. Note: Setpoints can only be changed when the starter is in the Ready Mode. Also the soft start will not start when it is in programming mode. 5.
TX Series 48 - 1250A 5.1.3 Phase and Ground Settings (Setpoint Page 3) Security Level Level 2 Password Protection Page 3 Phase and Ground Settings Setpoint Page Imbalance Alarm Level Factory Setting Default 15% FLA 5-30 %, Off Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec Imbalance Trip Level 20% 5-30 %, Off Imbalance Trip Delay 2.0 sec 1.0-20.0 sec Undercurrent Alarm Level Off 10-90 %, Off Undercurrent Alarm Delay 2.0 sec 1.0-60.
TX Series 48 - 1250A 5.1.4 Relay Assignments (Setpoint Page 4) Security Level Level 2 Password Protection Page 4 Relay Assignments Setpoint Page Description O/L Trip I/B Trip S/C Trip Overcurrent Trip Stator RTD Trip Non-stator RTD Trip G/F Hi Set Trip G/F Lo Set Trip Phase Loss Trip Accel.
TX Series 48 - 1250A 5.1.5 Relay Configuration (Setpoint Page 5) Security Level Level 2 Password Protection Page 5 Relay Configuration Setpoint Page Description Factory Setting Default Range Section Trip (AUX1) Fail-Safe No Yes or No SP5.1 Trip (AUX1) Relay Latched Yes Yes or No SP5.2 Alarm (AUX2) Fail-Safe No Yes or No SP5.1 Alarm (AUX2) Relay Latched No Yes or No SP5.2 AUX3 Relay Fail-Safe No Yes or No SP5.1 AUX3 Relay Latched No Yes or No SP5.
TX Series 48 - 1250A 5.1.6 User I/O Configuration (Setpoint Page 6) Security Level Lavel 2 Passowrd Protection Page 6 User I/O Configuration Setpoint Page Factory Setting Default Description Range Tachometer Scale Selection Disabled Enabled or Disabled Manual Tach Scale 4.0 mA: 0 RPM 0 - 3600 Manual Tach Scale 20.
TX Series 48 - 1250A 5.1.
TX Series 48 - 1250A 5.1.9 RTD Option Configuration (Setpoint Page 9) Security Level Level 3 Password Protection Page 9 RTD Configuration Setpoint Page Factory Setting Default Description Range Section Use NEMA Temp for RTD Values Disabled Enabled or Disabled # of RTD Used for Stator 4 0-6 SP9.2 RTD Voting Disabled Enabled or Disabled SP9.
TX Series 48 - 1250A 5.1.
TX Series 48 - 1250A 5.1.
TX Series 48 - 1250A 5.2 Setpoint Menu MENU (1) Note: 1. Push MENU key to toggle the screens between Setpoint Menu and Metering Menu. 2. Follow the arrow keys to get to different screens. Example: For Page 3 PHASE & GROUND SETTINGS, press the MENU key and the DOWN ARROW two times.
TX Series 48 - 1250A SP.1 Basic Configuration (Setpoint Page 1) In Setpoint Page 1, the TX is looking for the following basic nameplate data of the motor. SP1.1 Motor Full Load Amps: Allows the user to enter the motor’s FLA rating. Range of adjustment is 50 - 100% (less programmed service factor). MENU PAGE 1 BASIC CONFIGURATION MOTOR FULL LOAD AMPS : 200 AMPS Range: 50 - 100% of Unit MAX CURRENT AMPS Increments of 1 SP1.
TX Series 48 - 1250A SP.2 Starter Configuration (Setpoint Page 2) MENU (Hit DOWN ARROW one time) PAGE 2 STARTER CONFIGURATION START CONTROL MODE : START RAMP 1 JOG, START RAMP 1, START RAMP 2, DUAL RAMP, CUSTOM ACCEL CURVE,START DISABLED If VOLTAGE selected these screens will appear. If CURRENT selected these screens will appear.
TX Series 48 - 1250A SP.2 Starter Configuration (Setpoint Page 2) Provides multiple choices for starting ramps that can be selected for particular loads and applications. SP2.1 Start Control Mode: Dual Ramp, Custom Accel Curve, Tach Ramp, Jog Voltage, Start Ramp 1, Start Ramp 2. • Dual Ramp: The dual ramp mode works in conjunction with External Input #3. This allows the user to switch between the two start ramps without having to reconfigure the start mode.
TX Series 48 - 1250A either VOLTAGE or CURRENT. • Initial Torque (Initial Voltage #1 or Initial Current #1): Sets the initial start point of either the Voltage Ramp or the Current Ramp. Every load requires some amount of torque to start from a standstill. It is inefficient to begin ramping the motor from zero every time, since between zero and the WK2 break-away torque level, no work is being performed.
TX Series 48 - 1250A MENU (Hit DOWN ARROW two times) PAGE 3 PHASE & GROUND SETTINGS SP.3 Phase & Ground Settings (Setpoint Page 3) (Security Level: 2) Note: Proper phase sequence must be observed when connecting the input power. For example, phase A must lead phase B, which in turn must lead phase C by 120° respectively. If the phase rotation is not correct, a fault light and the LCD display will indicate the problem. SP3.1 Imbalance Alarm Level: This is an advance warning of a phase imbalance problem.
TX Series 48 - 1250A SP.3 Phase & Ground Settings (Setpoint Page 3) continued MENU (Hit DOWN ARROW two times) PAGE 3 PHASE & GROUND SETTINGS SP.3 Phase & Ground Settings (Setpoint Page 3) (Security Level: 2) SP3.5 Overcurrent Trip Level: Typically used to indicate the motor is severely overloaded and at which point a trip occurs. • Overcurrent Trip Delay: The amount of time the overcurrent condition must exist before a trip will occur. SP3.
TX Series 48 - 1250A SP3.12 Overvoltage Trip Level: Typically used to indicate that the line voltage is too high and at which point a trip occurs SP3.19 Power Factor Lag Trip: The acceptable amount of power factor lag before a trip is generated. • Power Factor Lag Delay: The amount of time that the power factor lag condition must exist beyond the window before a trip will occur. • Overvoltage Trip Delay: The amount of time that the overvoltage condition must exist before a trip will occur. SP3.
TX Series 48 - 1250A SP.
TX Series 48 - 1250A SP.4 Relay Assignment (Setpoint Page 4) (Security Level: 2) All of the protection functions of the TX are user programmable to an output relay. The factory will ship with all tripping functions assigned to TRIP (AUX1) relay, and all alarm functions to ALARM (AUX2) relay. Note: AUX1 - 4 are Factory Set and should not be changed. SP4.1 The following is a list of all the user programmable functions. Note: The Relay Assignments are factory defaults.
TX Series 48 - 1250A SP.5 Relay Configuration (Setpoint Page 5) (Security Level: 2) In Setpoint Page 5 the user can configure the four output relays as either fail-safe or non fail-safe and latching or non-latching. MENU (Hit DOWN ARROW four times) PAGE 5 RELAY CONFIGURATION TRIP (AUX1) RELAY FAIL-SAFE: NO TRIP (AUX1) RELAY LATCHED: YES Options: Yes or No SP5.1 When a relay has been configured as fail-safe and power is applied, the relay will be energized.
TX Series 48 - 1250A SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2) ENABLED PAGE 6 USER I/O CONFIGURATION TACHOMETER SCALE SELECTION: DISABLED Options: ENABLED or DISABLED MANUAL TACH SCALE 4.0 mA: 0 RPM Range: 0-3600 Increments of 5 MANUAL TACH SCALE 20.0 mA: 2000 RPM TACH ACCEL TRIP MODE SELECT: DISABLED Range: 0-3600 Increments of 5 TACH RAMP TIME : 20 SEC Range: 1 - 120 SEC.
TX Series 48 - 1250A SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2) The TX can be configured to accept a tachometer feedback signal through the 4-20mA input and has two options available for scaling the tachometer input. Note: At the time of this printing, SP6.1 - SP6.4 are pending. SP6.1 The first screen of setpoint page 6 is TACHOMETER SCALE SELECTION. When this is set to AUTO, the display prompts the user to program the TX to sense when the motor speed is zero.
TX Series 48 - 1250A SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2) USER PROGRAMMABLE EXTERNAL INPUTS (Continued) EXTERNAL INPUT #1 SELECT: DISABLED Options: Enabled or Disabled EXTERNAL INPUT #2 SELECT: DISABLED Options: Enabled or Disabled DUAL RAMP SELECT: DUAL RAMP Options: Enabled, Disabled or Dual Ramp THERMOSTAT SELECT: ENABLED Options: Enabled, Disabled or Thermostat NAME EXT.
TX Series 48 - 1250A SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3) MENU (Hit DOWN ARROW six times) PAGE 7 CUSTOM ACCELERATION CURVE CUSTOM ACCEL CURVE : DISABLED Range: DISABLED, CURVE A, B or C SP7.1 Setpoint Page 7 allows the user to custom design the acceleration curve (start curve) to the specific application. The user can custom design up to three different curves in the TX. Only one curve can be active (enabled) at a time.
TX Series 48 - 1250A SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3) CUSTOM CURVE A CURVE A VOLTAGE LEVEL 8: 100% CUSTOM CURVE B Range: 0 - 100% Increments of 1 CURVE A RAMP TIME 8: 2 SEC CURVE B RAMP TIME 7: 2 SEC.
TX Series 48 - 1250A SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3) SP7.1 Setpoint Page 7 allows the user to custom design the acceleration curve (start curve) to the specific application. The user can custom design up to three different curves in the TX. Only one curve can be active (enabled) at a time. Each of the three curves has eight voltage levels, with corresponding ramp times and a current limit setting.
TX Series 48 - 1250A SP.8 Overload Curve Configuration (Setpoint Page 8) (Security Level: 3) MENU (Hit DOWN ARROW seven times) PAGE 8 OVERLOAD CURVE CONFIGURATION Configures the unit’s start and run protection mode. The unit has independent start and run curve protection and the settings can be based on the OL Class or set by the motor’s locked rotor current and time. SP8.
TX Series SP.9 RTD Configuration (Setpoint Page 9) (Security Level: 3) 48 - 1250A Please note, this is supplied as an option. Contact factory for more information.
TX Series 48 - 1250A SP.9 RTD Configuration (Setpoint Page 9) (Security Level: 3) The TX is available with an optional RTD card that provides 12 programmable RTDs which are individually programmable for type. The available types are 100 ohm platinum, 100 ohm nickel, 120 ohm nickel and 10 ohm copper. Each RTD can be identified with a description name of up to 15 characters (including spacing). Also, each individual RTD has it own alarm and trip level. SP9.
TX Series 48 - 1250A SP.10 Set Password (Setpoint Page 10) (Security Level: 3) MENU The TX has three levels of user programmable setpoint screens. Level one setpoints do not require a password because the data contained in level one is basic nameplate data and starter control. Level two setpoint screens require a three-digit password to configure the protection schemes. Level three setpoint screens require a four-digit password to access the full range of protection and starter schemes. SP10.
TX Series 48 - 1250A SP.11 Communications (Setpoint Page 11) (Security Level: 3) MENU SP11.1 Set Front Baud Rate: Configures the RS232 communications baud rate. (Hit DOWN ARROW ten times) SP11.2 Set Modbus Baud Rate: Configures the modbus communications baud rate. SP11.3 Modbus Address Number: Assigns a Modbus address to the TX relay. SP11.4 Set Access Code: Assigns an access code to the Modbus addressing. PAGE 11 COMMUNICATIONS SET FRONT BAUD RATE: 9.6 KB/SEC Range: 2.4, 4.8, 9.6, 19.2 38.
TX Series 48 - 1250A SP.
TX Series 48 - 1250A SP.12 System Setpoints (Setpoint Page 12) (Security Level: 3) SP12.1 Default Display Screen: This setpoint group allows the user to choose the default screen the TX displays while the motor is running. Select the metering page number (1-3), then select the metering screen number. The range varies depending on the selected page. To display a default screen, program the following two setpoints: • Metering Data Page#: Range is Page 1 - 3.
TX Series 48 - 1250A SP.13 Calibration & Service (Setpoint Page 13) (Security Level: Factory Use Only) MENU (Hit DOWN ARROW twelve times) PAGE 13 CALIBRATION & SERVICE SET DATE AND TIME ##/##/## ##:## ENTER DATE (DDMMYYYY) :##/##/#### Range: D = 1 - 31, M = 1-12, Y = 1970 - 2069 Increments of 1 MODEL #: ###### FIRMWARE REV. #: ###### PRESS ENTER TO ACCESS FACTORY SETTINGS SP.
TX Series 48 - 1250A Chapter 6 - Metering Pages The TX Series offers performance metering which gives the user the ability to view information about the motor and the TX unit. 6.1 Metering Page List The following charts list each Metering Page and the functions within that page. The applicable section of the manual is also referenced. 6.1.
TX Series 48 - 1250A 6.1.4 Status (Metering Page 4) Page 4 Status Metering Page Description of Display Screen Current status 1 Amount of time remaining before an overload trip occurs 2 Amount of time remaining from a thermal inhibit signal 3 Coast down time remaining 4 Amount of time remaining before a start command can be given 5 Excessive number of starts per hour 6 6.1.
TX Series 48 - 1250A 6.2 Metering Menu (1) Push MENU key to toggle the screens between Setpoint Menu and Metering Menu and follow the arrow keys to get to different screens.
TX Series 48 - 1250A MP.1 Metering Menu & Data (Metering Page 1) Displays the basic current metering data: Screen 1: Phase A, B, C and ground fault current. Screen 2: MENU Displays the average current of the % of imbalance and the motor’s RPM (available with tachometer input) METERING PAGE 1 CURRENT METERED DATA Screen 3: Displays the motor load in percent of motor FLA. Screen 4: Displays the line frequency and the present Phase Order.
TX Series MP.2 48 - 1250A Metering (Metering Page 2) Displays the TX Series statistical voltage metering information. MENU Screen 1: Displays Phase A, B, C and Power Factor. Note: P/F: N/A Motor stopped P/F: LG #.## (Lagging) P/F: LD #.## (Leading) Screen 1 METERING PAGE 2 VOLTAGE & POWER DATA Screen 2: Displays Phase A, B, C and Ground Fault Current. Vab: ### Vbc: ### Vca: ### P/F: ## #.## Screen 2 IA: ##### IB: ##### IC: ##### G/F:###.
TX Series 48 - 1250A METERING PAGE 3 RTD VALUES HOTTEST STATOR RTD#: # @ ### C Screen 2 MP.3 RTD Values (Metering Page 3) HOTTEST NON-STATOR RTD#: # @ ### C Displays the RTD information (when RTD option is supplied) Screen 3 Screen 1: Displays the hottest stator RTD (#1 - 6 depending upon number of RTDs used for stator). STATOR PHASE A1 RTD #1: ### C = ### F Screen 5 Screen 2: Displays the hottest non-stator RTD (#7-12 if #1-6 is used for stator).
TX Series MP.4 48 - 1250A Status (Metering Page 4) Displays the present status of the TX Series soft start. MENU Screen 1 (See note at left) Screen 1: Displays the present state of the unit as follows: METERING PAGE 4 STATUS (CURRENT STATUS) Screen 2 Screen 2: Displays the amount of time remaining before an overload trip will occur. O/L TRIP LEFT TO TRIP: ###### SEC Screen 1 Note: CURRENT STATUS Screens include: 1.
TX Series MP.
TX Series MP.6 48 - 1250A Last Trip (Metering Page 6) Displays the information regarding the last trip. MENU Screen 1: Displays the cause of the last trip. Screen 1 Screen 2: Displays the measured phase current at the time of the trip. METERING PAGE 6 LAST TRIP (cause of trip) (value at time of trip) Screen 2 Screen 3: Displays the Vab, Vbc, Vca and power factor at the time of trip. Ia: #### Ic: #### Screen 4: Displays the imbalance percentage, the frequency and the kW at the time of the trip.
TX Series 48 - 1250A MENU Screen 1 METERING PAGE 7 STATISTICS MP.7 MWH TOTAL : ### Screen 2 Statistics (Metering Page 7) Displays the TX Series statistical trip information. Screen 1: Displays the total of megawatt hours. Screen 2: Displays the accumulated total running hours. Screen 3: Clears the total running hour count. Screen 4: Displays the total number of trips since the last clearing the statistical data and the total number of short circuit trips.
TX Series 48 - 1250A Chapter 7 - Maintenance and Troubleshooting The TX Series is designed to be a maintenance-free product. However, as with all electronic equipment, the unit should be checked periodically for dirt, moisture or industrial contaminants. These can cause high voltage arc-over, carbon tracking or prevent proper cooling of the SCR heat sinks. All bolts should be checked annually for proper tightness using an accurate torque wrench .
TX Series Problem 48 - 1250A CPU LCD Display LED Aux Relay Possible Cause Improper programming Overload OVERLOAD TRIP Trip Solutions Check motor nameplate versus programmed parameters AUX1 Possible load damage or Check motor currents jammed load Stall prevention ACCEL TIME TRIP Trip AUX1 Improper setting for motor Verify current limit setting load condition Damaged load Under Current Trip UNDER CURRENT TRIP Trip AUX1 Self-test Failure SELF-TEST FAILURE Trip AUX1 Check for load failure
TX Series Problem 48 - 1250A CPU LCD Display LED Aux Relay Possible Cause Solutions No control voltage applied Apply control voltage to TB1 pins 1 and 6 on the power board to control board Control power transformer Remove power and replace the power failure or CPT fuse failure transformer or the CPT fuse Motor will not start Any fault indication message Trip AUX1 Start circuit wired incorrectly Remove power and correct the start circuit wiring No start command Apply the start command No 3 pha
TX Series 48 - 1250A 7.2 SCR Testing Procedure WARNING Failure to remove both line and control power before starting this procedure may cause personal injury or death. Remove both line power and control power from the unit and lock out. Disconnect any two motor load leads and any two line leads. Disconnect the SCR connections to main control board J5, J6 and J7. Refer the Chapter 6 for the main control board layout. Note the type of color coding of the wires connected to J5, J6 and J7.
TX Series 48 - 1250A 7.3 Replacing SCR Devices Two types of SCRs are used in the TX Series depending on the horsepower/ amperage rating of the unit. Isolated SCRs are used in smaller units and “hockey puck” type SCRs are used in larger units. (Refer to Chapter 9 for the main control board layout.) 7.3.1 Changing an Isolated SCR • Remove both line and control power from unit, tag and lock out.
TX Series 48 - 1250A 7.3.2 Changing a Hockey Puck Type SCR • Remove both line and control power from unit, tag and lock out. WARNING Failure to remove both line and control power before starting this procedure may cause personal injury or death. • Toshiba uses two types of clamps with gauges for reading the amount of force on the device. The first type of force gauge uses a spin washer. When the proper force is applied, the washer will be free to spin.
TX Series 48 - 1250A Once proper force is reached make sure that the SCR pucks are securely held between the heatsinks and aligned evenly. • Replace any lugs, MOVs, snubbers, power straps, printed circuit boards and associated wiring that was removed in step 4. Use the following chart to verify wiring of J5, J6 and J7: • 7.4 After verifying that all wiring is correctly connected, test the SCR and then test the unit.
TX Series 48 - 1250A 7.
Tach Input (+) TOSHIBA- 75 User Input #3 (-) User Input #4 (-) Unit #2 User Input #4 (+) 2 or 4 wire Modbus TB1 User Input #3 (+) User Input #2 (-) User Input #2 (+) User Input #1 (-) User Input #1 (+) Thermal Reg. Dump (-) Thermal Reg. Dump (+) Fault Reset Input (-) Fault Reset Input (+) Program Enable Input (-) Program Enable Input (+) Cal. Input (-) Cal.
TX Series 48 - 1250A 7.6 MAINTENANCE PROGRAM In order to ensure continued reliable and safe operation of the equipment, a program of periodic maintenance must be established. Operating and environmental conditions will usually dictate the frequency of inspection required. NFPA Publication 70B “Electrical Equipment Maintenance” may be used as a guide for setting up the maintenance program. DANGER Contact with energized components can cause severe injury, death and property damage.
TX Series 48 - 1250A 7.7 DISPOSAL/STORAGE DISPOSAL Contact your state environmental agency for details on disposal of electrical components and packaging in your particular area. STORAGE If the starter is to be stored for any length of time prior to installation, the following precautions should be taken: 1) The original packing should be restored, if possible. 2) Do not subject the equipment to moisture or sun rays. Store in cool, clean, and dry location.
TX Series 48 - 1250A Appendix A - Reference Section Typical Full Load Current for 3 Phase Motors INDUCTION TYPE SQUIRREL CAGE AND WOUND ROTOR (AMPERES) SYNCHRONOUS TYPE UNITY POWER FACTOR* (AMPERES) HP 115V 200V 208V 230V 460V 575V 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 4.4 6.4 8.4 12 13.6 2.5 3.7 4.8 6.9 7.8 11 17.5 25.3 32.2 48.3 62.1 78.2 92 120 150 177 221 285 359 414 552 2.4 3.5 4.6 6.6 7.5 10.6 16.7 24.2 30.8 46.2 59.4 74.
TX Series 48 - 1250A Typical Maximum Locked Rotor Current THREE PHASE SQUIRREL CAGE MOTORS HP NEMA B, C & D 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 HP NEMA E 0.5 0.75 1 1.5 2 3 5 7.
TX Series 48 - 1250A Cooling Consideration for Maintaining Ambient Temperature RATED CURRENT UNITS = AMPS 48 78 120 180 220 288 414 476 550 718 1006 1150 1250 HEAT GENERATED UNITS = WATTS 216 351 540 810 990 1296 1863 2138 2475 3231 4527 5175 5625 MINIMUM CFM UNITS = CFM 38 62 95 143 174 228 328 376 436 569 797 911 990 TOSHIBA - 80 MINIMUM EXP. S.S. UNITS = SQ.FT.
TX Series 48 - 1250A Appendix B - Record of Setpoint Adjustments Page 2 Starter Configuration Setpoint Page Level 1 No Passowrd Required Security Level Security Level Level 1 No Passowrd Required Page 1 Basic Configuration Setpoint Page Factory Setting Default Description Range Motor Full Load Amps (FLA) Model dependent 50 - 100% of Unit Max Current Rating (Model and Service Factor dependent) Service Factor 1.15 1.00 – 1.
TX Series Security Level Level 2 Password Protection Page 3 Phase and Ground Settings Setpoint Page 48 - 1250A Imbalance Alarm Level Factory Setting Default 15% FLA Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec Imbalance Trip Level 20% 5-30 %, Off Imbalance Trip Delay 2.0 sec 1.0-20.0 sec Undercurrent Alarm Level Off 10-90 %, Off Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec Overcurrent Alarm Level Off 100-300 %, Off Description Range 5-30 %, Off Overcurrent Alarm Delay 2.0 sec 1.
TX Series Security Level Level 2 Password Protection Page 4 Relay Assignments Setpoint Page 48 - 1250A Description O/L Trip I/B Trip S/C Trip Overcurrent Trip Stator RTD Trip Bearing RTD Trip G/F Hi Set Trip G/F Lo Set Trip Phase Loss Trip Accel.
TX Series Setpoint Page Security Level Level 2 Password Protection Page 5 Relay Configuration Setpoint Page Security Level 48 - 1250A Lavel 2 Passowrd Protection Range Trip (AUX1) Fail-Safe No Yes or No Trip (AUX1) Relay Latched Yes Yes or No Alarm (AUX2) Fail-Safe No Yes or No Alarm (AUX2) Relay Latched No Yes or No AUX3 Relay Fail-Safe No Yes or No AUX3 Relay Latched No Yes or No AUX4 Relay Fail-Safe No Yes or No AUX4 Relay Latched No Yes or No Factory Setting Default De
TX Series Setpoint Page Security Level 48 - 1250A Description Custom Accel Curve Factory Setting Default Range Disabled Disabled, Curve A, B, or C Curve A Voltage Level 1 25% 0-100% Curve A Ramp Time 1 2 sec 1-60 sec Curve A Voltage Level 2 30% 0-100% Setting Setpoint Page Level 3 Password Protection Page 7 Custom Acceleration Curve Custom Curve A Security Level Curve A Ramp Time 2 2 sec 1-60 sec Curve A Voltage Level 3 37% 0-100% Curve A Ramp Time 3 2 sec 1-60 sec Curve A Vol
TX Series Security Level Level 3 Password Protection Page 9 RTD Configuration Setpoint Page 48 - 1250A Factory Setting Default Description Range Use NEMA Temp for RTD Values Disabled Enabled or Disabled # of RTD Used for Stator 4 0-6 RTD Voting Disabled Enabled or Disabled Stator Phase A1 Type Off 120 OHM NI, 100 OHM NI, 100 OHM PT, 10 OHM CU RTD #1 Description Stator A1 User defined, Up to 15 Characters Stator Phase A1 Alarm Level Off 0-240C (32-464F), Off Stator Phase A1 Trip Leve
TX Series Setpoint Page Security Level 48 - 1250A Level 3 Password Protection Level 3 Security Level Level 3 Password Protection Setpoint Page Page 11 Communiications Security Level Page 10 Page 9 RTD Configuration RTD #10 Type Setpoint Page Factory Setting Default Description Range Off Same as Stator Phase A1 RTD #10 Description User defined User defined, Up to 15 Characters RTD #10 Alarm Level Off 0-240C (32-464F), Off RTD #10 Trip Level Off 0-240C (32-464F), Off RTD #11 Type Off
TX Series Setpoint Page 48 - 1250A Security Level Factory Setting Default Description Range Setting Default Display Screen Metering Data Page # Metering Data Screen # 1 Enter Metering Page (1-4) 1 Enter Metering Screen Page 1(1-10) Page 2 (1-11) Page 3 (1 - 29) Page 4 (1 - 6) Disabled Enabled or Disabled Alarms Level 3 Password Protection Page 12 System Setpoints RTD Failure Alarm Thermal Register Alarm 90% Off, 40-95% Thermal Alarm Delay 10 sec 1-20 sec O/L Class O/L Class (5-30) o
TX Series 48 - 1250A Warranty Policy Toshiba International Corporation ("Company") warrants that all equipment and parts described herein will be free from defects in materials and workmanship.