Maintenance Guide
Table Of Contents
- Introduction
- FTElectric Manual v2.2.0.0 (CDL)
- Types of Electric Fire Pump Controllers
- Methods of Starting/Stopping
- FCC Regulations and Radio Standards Specification (RSS) Rules
- Location
- Mounting
- Storage
- Wiring and Connections
- Water Connections
- Electrical Wiring
- Electrical Connections
- Energy Consumption
- Sizing
- Incoming Power Connections
- Motor Connections
- Terminal Strip Descriptions
- Quick Start-Up Guide
- The Mark III
- Alarm Bell
- First Setup
- Mark III: Manual Rebooting Method
- Pressure Transducer Test
- Home (Menu)
- Screen Saver
- Alarms (Menu)
- Config (Menu)
- History (Menu)
- Service
- Installation
- Main Features
- Home
- Alarms
- Configuration
- History
- Service
- Download Manuals
- Language
- Technical Documents
14
Mark III: Manual Rebooting Method
If required, here is the procedure to manually reboot the Mark III:
1- Turn OFF all disconnecting means to de-energize the Mark III. The Mark III's screen should turn black.
2- Press the stop button or wait until the Mark III's LED extinguishes.
3- Wait 10 seconds.
4- Turn ON all disconnecting means.
Pressure Transducer Test
The controller will test the pressure transducer at least once a week if no manual run test or no weekly test has been
conducted. During the test, the pressure reading will drop to zero but the controller will not see it as a starting request.
This pressure drop will be recorded in the “Pump Curve” page and in the logs with the message.
Home (Menu)
Home
The home page displays all controller statuses and important values of the controller. This includes all voltages, currents,
pressures, motor state and status
Navigation bar: Pressing this icon will open a navigation menu on the left side of the screen:
1. Go to Home page
2. Go to Alarms page
3. Go to Configuration page
4. Go to History page
5. Go to Service page
6. Go to Download Manual page
Home