Maintenance Guide
Table Of Contents
- Introduction
- FTElectric Manual v2.2.0.0 (CDL)
- Types of Electric Fire Pump Controllers
- Methods of Starting/Stopping
- FCC Regulations and Radio Standards Specification (RSS) Rules
- Location
- Mounting
- Storage
- Wiring and Connections
- Water Connections
- Electrical Wiring
- Electrical Connections
- Energy Consumption
- Sizing
- Incoming Power Connections
- Motor Connections
- Terminal Strip Descriptions
- Quick Start-Up Guide
- The Mark III
- Alarm Bell
- First Setup
- Mark III: Manual Rebooting Method
- Pressure Transducer Test
- Home (Menu)
- Screen Saver
- Alarms (Menu)
- Config (Menu)
- History (Menu)
- Service
- Installation
- Main Features
- Home
- Alarms
- Configuration
- History
- Service
- Download Manuals
- Language
- Technical Documents
10
Press “Motor Rotation”
Press the “Start” button to start the electric motor and validate that the electric motor is rotating in the correct direction. If
it is not rotating in the correct direction adjust the motor connections as per below. Press the “Stop” button to stop the
electric motor.
Acknowledge that the motor is tunring in the right direction by checking the
Check on Normal Power
selector box.
Once the motor rotation has been checked, go back to the controller start-up page and press the “Verify pressure” button.
WARNING!
On a Wye-Delta closed transition starter, if the transition from Wye to Delta occurs (after 5 to 8 seconds depending on the
motor HP), the manual stop push button will be disabled for 80 seconds. To stop the engine before the end of the 80 second
delay, use the disconnecting mean handle.