Maintenance Manual
37
It is possible to reload a past configuration by pressing the "reload configuration" button. Dates with an "*" are
settings following a "Service".
Do not change a parameter on this page without previously consulting a Tornatech representant.
Interlock Lockout
Config > Advanced > Interlock Lockout
This page is used to configure the Lockout input and the Interlock output parameters. To be active those options
need to be assigned to an Input or an Output on the IO board.
Lockout is an Input that prevents the motor from starting.
-Shutdown Motor: If enabled, the lockout signal will also act as a shutdown and will stop the motor if it is running.
-Enable in Manual: If checked, activation of the lockout input will prevent the Manual start.
-Enable in Automatic: If checked, activation of the lockout input will prevent the Automatic start.
-Enable in Remote: If checked, activation of the lockout input will prevent the Remote start.
-Enable in Flow: If checked, activation of the lockout input will prevent the Flow start.
Interlock is an Output that prevents a second motor from starting.
-Main coil required: If enabled, the controller will wait to have the main starting coil signal before putting Interlock
active.
-Enable in manual: If checked, this option will activate the output Interlock on a Manual start.
-Enable in auto: If checked, this option will activate the output Interlock on an Automatic start.
-Enable in remote manual: If checked, this option will activate the output Interlock on a Remote Manual start.
-Enable in start stop: If checked, this option will activate the output Interlock on a Start Stop mode.