Maintenance Manual

31
Sequential Start Timer
This timer sets the time delay between a demand becoming active and the starting of the motor. (Optional).
Time Range: 0-3600 Seconds
Run Period Timer
This timer sets the time the motor will keep running after the demand is resolved.
Time Range: 1-1440 Minutes
Alarms
Configuration > Advanced > Alarms
Most alarms are not configurable in the field, but some are with the appropriate password level. If it's configurable,
the checkboxes will be in white. Otherwise the checkboxes will be grey. Also, the two last fields: Value Usage and
Analog Value are not always visible.
Start Test: The alarm can be tested using this button. This test will only announce the chosen alarm. It will activate
the buzzer if the alarm is audible and will activate any output relays associated with this alarm. The test will not
activate other common alarms or other components. To stop the testing, press the “Stop Test” button.