Maintenance Manual
24
Alarms (Menu)
Configuration > Advanced > Alarms
This page displays the list of currently active and occurred alarms. Alarms with adjustable parameters can be set in
the Config ˃ Advanced ˃ Alarms pages (see section 6).
An alarm is called ACTIVE when its triggering condition is still valid.
An alarm is called OCCURRED when its triggering condition has been active, but is no longer true.
Alarms representing serious concerns will have a red triangle with an exclamation point in the center at the end of
the alarm message.
Alarms representing simple warnings will have a yellow triangle with an exclamation point in the center at the end of
the alarm message.
Pressing on the Buzzer Test button will ring the buzzer for three seconds.
To silence the buzzer, press the SILENCE button.
Pressing on the RESET button will reset OCCURRED alarms only.
Alarms ending with ** are available on transfer switch models only
The table displays system events:
- Date and time stamp of the alarm in the YYYY.MM.DD HH:mm:SS format
- Alarm message
- State: OCCURRED or ACTIVE
- Color Code Icon:
Red: The event is an alarm
Yellow: The event is a warning
Complete list of alarms :
- Normal Phase Reversal: Activates when the phase order on the normal power does not match the correct value of
the controller. Each time a service is acknowledged on the ViZiTouch, the controller synchronises the correct phase
order to the one detected on the normal power.
- Phase Loss L1: This alarm is activated if the first phase of the normal power connection does not meet the
qualification criteria.
- Phase Loss L2: Activates if the second phase of the normal power connection does not meet the qualification
criteria.
Alarms