Maintenance Manual

15
Verify that the normal voltage shown at L1-L2, L2-L3 and L1-L3 (nominal) is the same as what is written on the fire
pump controllers nameplate. The fire pump controller will validate the nominal voltage automatically versus what it
has been built for.
If all is adequate green check marks will appear.
To continue to next step, press “ ˂ First Start Up “
Press “Motor Rotation”
Press the “Start” button to start the electric motor and validate that the electric motor is rotating in the correct
direction. If it is not rotating in the correct direction adjus the motor connections as per below. Press the “Stop”
button to stop the electric motor.