  Character 
 PV screen  
 Auxiliary screen  
Designation  Description  Initial value 
18
ch 
Set an AT 
sensitivity 
Thermocouple input 
 Setting range:  0 to 999 or 0.0 to 999.9 
 Setting unit:  °C 
Resistance bulb input 
 Setting range:  0 to 999 or 0.0 to 999.9 or 0.00 to 
999.99 
  (when the input type is,
 ,
or
) 
 Setting unit:  °C 
Current and voltage inputs 
 Setting range:  0 to 99999 
  The decimal place can be set to a 
desired position. 
 Setting unit:  digit 
      CH2 only 
Potentiometer input 
 Setting range:  0.0 to 999.9 
 Setting unit:  % 
19
□ch 
Set a proportional 
band for the main 
output 
Setting range:  0.0 to 200.0 
Setting unit:  % of
ch to
ch 
20
□□ch 
Set an integration 
time for the main 
output 
Setting range:  0 to 3,600 seconds 
21
□□ch 
Set a derivative 
time for the main 
output. 
Setting range:  0 to 3,600 seconds 
22
□ch 
Set a proportional 
cycle for the main 
output 
Setting range:  1 to 120 seconds 
23
ch 
Anti-reset windup
Setting range:  0.0 to 100.0 (-10.0 to -110.0: in analog 
output) 
Setting unit:  % 
24
ch 
Set an upper limit 
for the main output 
operation amount 
limiter 
Setting range:  Set a lower limit for the operation amount 
limiter to 100.0 (-110.0: in analog output) 
Setting unit:  % 
25
ch 
Set a lower limit 
for the main output 
operation amount 
Setting range:  Set the system to 0.0 (-10.0: in analog 
output) to an upper limit for the operation 
amount limiter 
Setting unit:  % 
26
ch 
Manual reset  Setting range:  0.0 to 100.0 
  -100.0 to 100.0 (heating/cooling) 
Setting unit:  % 