User guide
  - 13 - 
Example: 
Assume the following for various settings and PV: 
PV = 120 C, operation amount limiter point 2 = 75.0%, current value limiter point 2 = 10.0 A, present operation 
amount = 60.0% and AHC = 1.0 A.   
  If measured current valued = 15 A: 
  Based on the relation [0 to present operation amount (60.0%) = 0.0 to measured current value (15.0 A)], the 
operation amount [current value limiter point 2 (10.0 A) - current limiter sensitivity (1.0 A)] is to be determined.   
  The calculation results in the operation amount of 36.0%.   
15A
Current
0% 60.0%
15A
Current
0% 60.0%36.0%
(10A-1A =)9A
0A0A
Operation 
amount
Operation 
amount
*  The operation limiter point 2 = 75.0%; as this amount is larger than the operation amount resulted from the 
calculation, the operation amount is eventually limited at 36.0%.   
4.14.3  Other operation amounts limiter setting 
4.14.3-1 Primary/secondary control operation amount change limiter increase setting 
Setting items: 
Primary/secondary control operation amount change limiter increase setting: 0.0 to 549.9 [%] (no function by 
setting at 0.0 [%]) 
Operation description: 
The increase rate of variation of a calculated operation amount is limited.   
The operation amount allowed to increase for a second is set in percent.   
The setting is effective during AT.     
If the setting is changed, control results also changes; redo AT.   
If the setting is 100%, the variation increases only up to 20 % for input sampling (200 ms).   
To increase up to 100% for input sampling (200 ms), set at 500%.   
(1 second  200 ms)  100% = 500% 
Calculated operation 
amount
Limited operation 
amount
100%
100%
0%
0%
Time