INSTRUCTION MANUAL EMERGENCY POWER SUPPLY POWER SUPPLY FRAME POWER SUPPLY UNIT VX-2000DS ER VX-2000DS UK VX-2000DS SA VX-2000PF VX-200PS ER VX-200PS UK VX-200PS SA 1134 TOA Electronics Europe GmbH Suederstrasse 282, 20537 Hamburg, Germany 1134-CPR-083 14 DoP 1134-CPD-083 EN 54-4: 1997/A1: 2002 + A2: 2006 Power supply equipment for fire detection and fire alarm systems for buildings VX-2000DS ER/UK, VX-200PS ER/UK (Does not apply to VX-2000DS SA and VX-200PS SA) Thank you for purchasing TOA's Emergency
TABLE OF CONTENTS 1. SAFETY PRECAUTIONS ................................................................................. 3 2. NOMENCLATURE AND FUNCTIONS 2.1. VX-2000DS Emergency Power Supply .............................................................. 5 2.2. VX-200PS Power Supply Unit ............................................................................ 7 2.3. VX-2000PF Power Supply Frame ...................................................................... 8 3. INSTALLATION 3.1.
1. SAFETY PRECAUTIONS • Before installation or use, be sure to carefully read all the instructions in this section for correct and safe operation. • Be sure to follow all the precautionary instructions in this section, which contain important warnings and/or cautions regarding safety. • After reading, keep this manual handy for future reference. WARNING Indicates a potentially hazardous situation which, if mishandled, could result in death or serious personal injury.
CAUTION Indicates a potentially hazardous situation which, if mishandled, could result in moderate or minor personal injury, and/or property damage. When Installing the Unit • (Applicable to VX-2000DS and VX-200PS only) Never plug in nor remove the power supply plug with wet hands, as doing so may cause electric shock. • (Applicable to VX-2000DS and VX-200PS only) When unplugging the power supply cord, be sure to grasp the power supply plug; never pull on the cord itself.
2. NOMENCLATURE AND FUNCTIONS 2.1. VX-2000DS Emergency Power Supply • Up to 3 (6 ch) VX-200PS Power Supply units can be connected per VX-2000DS to supply backup DC power to individual components. • Automatically switches to the backup power supply when the DC power supply from the VX-200PS is interrupted. • Detects charging circuitry or battery failures, and transmits failure signals to the DS LINK of the TOA Voice Evacuation Systems (VX-2000, SX-2000, and VM-3000).
1. Power indicator [MAIN POWER] Lights green when both DC power from the VX200PS and AC power are supplied. 2. Battery connect indicator [BATTERY CONNECT] Lights green when the battery is connected. 8. PS detect switches Always connect a power supply to the terminals 1 + 2 of the DC INPUT. When connecting a power supply to the terminals 3 + 4 of the DC INPUT, set the PS2 switch to ON. When connecting a power supply to the terminals 5 + 6 of the DC INPUT, set the PS3 switch to ON. 3.
[Fault indication] If any of the Power indicator [MAIN POWER], Battery connect indicator [BATTERY CONNECT], Charging indicator [CHARGING], or Battery check indicator [BATTERY CHECK] on the front panel remains unlit, the unit is judged failed. In such cases, remove the cause of the failure, and restore the unit to normal operation. Note Even if any of these indicators flashes, this does not indicate malfunction. 2.2.
2.3. VX-2000PF Power Supply Frame The VX-2000PF permits the VX-200PS Power Supply to be mounted in an equipment rack. Up to 3 VX-200PS units can be installed in the VX-2000PF. Refer to p. 10 for the VX-200PS mounting procedure. [VX-2000PF Components] This unit is comprised of the following components. For the component assembly, refer to p. 9. 1. Front panel .................................................................. 1 2. Side panel ...................................................................
3. INSTALLATION 3.1. Assembling the VX-2000PF Power Supply Frame Self-tapping screw 4 x 10 (supplied with the VX-2000PF) Chassis Side panel Fixing bracket Side panel Front panel Note: Mount the front panel and fixing bracket after installing the VX-200PS units on the chassis. [Installation Precautions] The VX-2000PF and VX-200PS units are slightly different in specifications between the previous and current production lots.
3.2. Installing the VX-200PS Power Supply Unit in the VX-2000PF To be compliant with EN 54-4, install the VX-2000DS and VX-2000PF in the CR cabinet rack series CR-15, CR-22, CR-27, CR-35, CR-40, and CR-44. Step 1. Mount the VX-2000PF in an equipment rack. Step 2. Mount the VX-200PS in the VX-2000PF. Self-tapping screw 4 x 10 (remove from VX-200PS' rear panel) Supplied with the VX-2000PF or other appropriate screw VX-2000PF 1 1 2 Rack VX-200PS Step 3.
3.3. Battery Installation WARNING • Take special care to prevent the battery from being shorted by misconnection of the battery cable. If the short occurs, the unit may fail. Follow the instructions in this section for safe and secure connection. • Be sure to switch off the system power before battery connection. For the procedure, refer to p. 28 "SWITCHING OFF SYSTEM POWER.
• Strip the cable end long enough (30 mm ± 5 mm) to be fully clamped. Otherwise, its outer jacket prevents the cable conductor from being tightly secured, causing poor contact. Correct Incorrect [Attaching the insulating sheet] To prevent the battery cable from being shorted to the rear panel due to misconnection, attach the supplied insulating sheet in place following the procedures below. VX-2000DS Step 1. Remove the screw indicated by the arrow. BATTERY POWER IN 24V MAX150A Step 2.
• Use the battery connection cables as short in length and as large in diameter as possible.
[Disconnecting the Battery] Step 1. Confirm that battery power is not in use by means of the VX-2000DS' front-mounted BATTERY POWER LED, which is unlit in this case. Step 2. Loosen the VX-2000DS' BATTERY POWER IN negative terminal screw, then pull out the negative battery cable. Notes • Never remove the positive cable first to avoid battery short-circuit that occurs if the positive cable should contact the unit chassis or equipment rack.
[Fixing the battery] (ER/UK version only) To comply with EN 54-4, fix the battery at the bottom plate surface of the rack as shown below. Attach hook fasteners to the bottom surface of each battery, and loop fasteners to the bottom plate surface of the rack. Bottom of battery [Viewed from the battery's bottom surface side] Hook fasteners (supplied with the VX-2000DS) When replacing the batteries, 4 each of fastener hooks and loops, and a thermal insulating sheet listed below are also required.
4. CONNECTIONS WHEN USING WITH THE VX-2000 SYSTEM 4.1.
4.2. Connecting the VX-2000DS to VX-2000 System VX-2000 DATA LINK From VX-2000DS (+) (–) AUDIO LINK OUT a b DC POWER IN VX-2000SF 1 2 From VX-2000DS (+) (–) DS-SF LINK a b DC POWER IN VP-2064, VP-2122, VP-2241, or VP-2421 DC POWER IN 28 V 4.8 A From VX-2000DS (+) (–) CH3 CH1 CH4 CH2 CH3 CH1 CH4 CH2 PA OUT (SP LINE) CH4 C H CH3 C H CH2 C H CH1 C H a b VP-2064, VP-2122, VP-2241, or VP-2421 DC POWER IN 28 V 4.
5. CONNECTIONS WHEN USING WITH THE SX-2000 SYSTEM 5.1.
5.2. Connecting the VX-2000DS to SX-2000 System [When using a redundant power system*] In this connection example, 2 power supply units are used. Even if one of the 2 units fails or its power supply line is broken, power is still supplied from the other unit, preventing the system from going down.
[When not using a redundant power system] Required power is supplied to the system from a single power supply unit. Connect the [+] terminal of Input A to the [+] terminal of Input B, and the [–] terminal of Input A to the [–] terminal of Input B. SX-2100AO or SX-2000AO (The figure below shows the SX-2100AO.
5.3. DS Link Terminal Connections Connect the DS-SF LINK terminal of the VX-2000DS to the DS Link terminal of the SX-2000SM or SX2100AO. The figure below shows a connection example when the VX-2000DS units are connected to the SX2100AO. This connection also applies to the SX-2000SM. DS Link Terminals Applicable cable: Cat. 5 STP (Category 5 shielded twisted pair cable) SX-2100AO VX-2000DS (No.
6. CONNECTIONS WHEN USING WITH THE VM-3000 SYSTEM Cable: AWG 10 – AWG 8 (–)(–)(+)(+) From VX-2000DS Note Remove the short bar attached at the factory. VM-3240VA/3360VA d d c a 230 V AC 220 V AC 50/60 Hz VP-2241 DC POWER IN 28 V 4.8 A PA OUT (SP LINE) C From VX-2000DS (+) (–) H c d PA LINK VP-200VX PA LINK VP-200VX (–)(–)(+)(+) VM-3240E/3360E d d c From VX-2000DS Cable: AWG 10 – AWG 8 b 230 V AC 220 V AC 50/60 Hz VP-2241 DC POWER IN 28 V 4.
[Required number of VX-200PS and VX-2000DS units] The required number of the VX-2000DS Emergency Power Supply units and VX-200PS Power Supply Units are determined depending on the application of the system configured with the VM-3240VA, VM-3360VA, VM3240E, and VM-3360E (hereinafter called "VM amplifier"), and/or the VP-2241 and VP-2421 (hereinafter called "VP amplifier").
System including one VP amplifier connected as a standby amplifier One VX-2000DS is required every 3 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units 1 2 1 0 3 4 5 2 6 7 8 3 9 10 4 1 Below is an example showing that 2 VX-2000DSs and 1 VX-200PS are used in a system including 4 VM amplifiers. Note Connect the VX-200PS to the VX-2000DS to which the VP amplifier is connected. VM-3240VA EXT. AMP INPUT VX-200PS VM LINK EXT.
• Required number of VX-2000DS and VX-200PS units in a BGM/Paging system One each of the VX-2000DS and VX-200PS is required every 2 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units 1 2 1 1 3 4 2 2 5 6 3 3 7 8 9 4 4 10 5 5 Below is an example showing that 2 each of VX-2000DSs and VX-200PSs are used in a system including 3 VM amplifiers. VM-3240VA EXT. AMP INPUT VM LINK EXT. PA LINK PA OUT VP-2241 DC POWER VM-3240E VX-200PS VM LINK EXT. AMP INPUT EXT.
7. CABLE USAGE TABLE [VX-2000DS] Terminal to Connect Terminal Name AC IN Equipment Receptacle 3P inlet Cable Type Plug – Cable Type RJ45 (male) BATTERY POWER IN AWG 6 – AWG 0 (1/0) Unprocessed cable 16 – 50 mm2 end (line resistance within 4 mΩ/total) Cat. 5 STP AWG 18 – AWG 14 0.8 – 2.0 mm2 – DC POWER Screw terminal OUT AWG 24 – AWG 12 0.2 – 3.
8. USING THE VX-2000DS EXCLUSIVELY AS A BACKUP POWER SUPPLY The VX-2000DS can be used with the VM-2000 series system or other systems as a backup power supply unit which supplies battery power to the system when AC mains fail. To permit the VX-2000DS operation in this system configuration, shift the VX-2000DS' rear-mounted Setting switch to the AC position (factory-preset to the DC position).
9. SWITCHING OFF SYSTEM POWER (DC) When the system power (DC) needs to be switched off in such cases as maintenance or unit configuration change, shift the Setting switch on the VX-2000DS to the "AC" position following the procedure below. [To switch off the system power] Step 1. Terminate all current broadcasts to stop system operation. Step 2. Shift the Setting switch on the VX-2000DS rear panel to the "AC" position.
10. BLOCK DIAGRAM Control Connector [DS-SF LINK] BATTERY CONNECT Indicator DC Detect DC Input [PS IN] (150 A max.) DC Input 1 DC Input 2 Control Circuit DC Input 3 DC Input 4 DC Input 5 DC Input 6 Battery Connection Terminal [BATTERY POWER IN] Fuse 250 V AC T3.15 A L AC Mains 50/60 Hz MAIN POWER Fuse 40 A CHARGING DC Output 1 Charging Circuit NO NO Battery Check Switch NO NC Delay NO NO Fuse 7.
11. SPECIFICATIONS 11.1. VX-2000DS Emergency Power Supply Power Source Power Consumption Applicable Battery Charging Method Charging Current Charging Output Voltage Power Supply Input DC Power Output Control Connector Battery Connection Operating Temperature Finish Dimensions Weight 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz 240 W max. Panasonic LC-X1265PG/APG (65 Ah) Trickle charging 5 A max. 27.3 V ±0.
11.2. VX-200PS Power Supply Unit Power Source Power Consumption DC Power Output Ripple Voltage at Imax B (at VX-2000DS's DC Output) Operating Temperature Applicable Frame Finish Dimensions Weight 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz 580 W Rated output: 210 W (29 V, 7.25 A) x 2 Peak output: 400 W x 2 M4 screw terminal, distance between barriers: 11 mm Applicable cable diameter: AWG 14 – AWG 10 (line resistance within 10 mΩ/pair) Cross sectional area: 2.0 – 5.5 mm2 Max.
Traceability Information for Europe Manufacturer: TOA Corporation 7-2-1, Minatojima-Nakamachi, Chuo-ku, Kobe, Hyogo, Japan Authorized representative: TOA Electronics Europe GmbH Suederstrasse 282, 20537 Hamburg, Germany URL: http://www.toa.