Product Overview
TJERNLUND PRODUCTS, INC.
1601 Ninth Street White Bear Lake, MN 55110-6794
Phone: 651.426.2993 800.255.4208 Fax: 651.426.9547
Visit our web site: www.tjernlund.com
Copyright © 2011 Tjernlund Products, Inc. All rights reserved. P/N 8500650 Rev B
RT750 Series
as small as 8”
ID and as large
as 12” OD.
A
B
C
Tile Lined
Chimneys
RT1500 Series clamps to rectangular tile
liners 8” x 8” through 12” x 14” and
round tile liners from 10”-14”.
RT750 Series clamps
to rectangular tile
liners 6” x 6”
through 10” x 14”
and round tile
liners from 6”-11”.
RT1500 Series
as small as 12”
ID and as large
as 20” OD.
Metal Vents
Model RT750(H) RT1500(H)
Motor HP 1/12 1/2
Motor Amps 1.2 5.8
Motor Volts 120 120
Weight 35 lbs 55 lbs
ETL Listed to UL378, UL705
& CAN/CSA B255-M81
A 16” 21”
B 16” 21”
C 18” 24”
Inlet 8” 12”
Model RT750(H) RT1500(H)
Selection Guide for Gas & Oil Applications
Models RT750 & RT1500
MODEL VENT PIPE BTU/HR. INPUT, GAS WITH BTU/HR. INPUT, GAS/OIL MAX. EQUIVALENT** VENT
DIAMETER*
DRAFT HOOD/DIVERTER WITH BAROMETRIC CONTROL LENGTH (FT) @ 400
0
F
RT750 8"
400,000 to 700,000 500,000 to 900,000 100'
700,000 to 900,000 900,000 to 1,200,000 50'
RT750 10"
700,000 to 1,000,000 900,000 to 1,200,000 100'
1,000,000 to 1,200,000 1,200,000 to 1,500,000 50'
RT1500 12"
1,000,000 to 2,000,000 1,200,000 to 2,700,000 100'
2,000,000 to 2,400,000 2,700,000 to 3,200,000 50'
RT1500 14"
2,000,000 to 2,500,000 2,700,000 to 3,500,000 100'
2,500,000 to 2,700,000 3,500,000 to 3,700,000 50'
* Select inducer based on BTU/hr. input of appliance(s) rather than diameter of appliance vent
outlet or chimney.
**To determine equivalent ft., add the total length of straight vent pipe plus 10 ft. for each 90
0
elbow and 5 ft. for each 45
0
elbow.
MODEL
RT750H
RT1500H
MAXIMUM FACE AREA OF FIREPLACE‡
14 SQUARE FEET
28 SQUARE FEET
‡Determine vertical and horizontal face opening of hearth
in sq. ft. (If open on sides or back, total all openings)
Note: Due to their extended speed reduction capabilities, DCOP1
controlled inducers minimum burner inputs are reduced to
100,000 BTU/Hr. for all draft applications.
Selection Guide for Fireplaces and Ovens