Install Instructions
8
ADJUSTING THE EXHAUST PRESSURE SET POINT
The pressure set point is adjusted by positioning dip switches 6 - 1 to match the desired setting listed on the Pressure Setpoint
Table below. The factory set point is 0.10” W.C. The dip switches are located on the Red block on the top of the COP circuit board.
A dip switch is ON when pulled OUT towards you. A dip switch is OFF when pushed IN away from you.
CAUTION: Disconnect electrical power to COP L1 & N prior to adjusting dip switch settings.
ACCELERATION SPEED SETTINGS
Dip Switches 7-8 are used to select drive response time. Slow (30 sec) = 7 ON, 8 OFF, Medium (20 sec) = 7 OFF, 8 ON,
Fast (10 sec) = 7 ON, 8 ON,
The Fast (7 ON, 8 ON) acceleration is the factory default. Acceleration adjustment is typically not required unless set points of
greater than 0.30” W.C. are selected or if the vent run is a long length.
654321
-0.05 IN IN OUT OUT OUT OUT
-0.06 IN OUT IN IN IN IN
-0.06 IN OUT IN IN IN IN
-0.07 IN OUT IN IN IN OUT
-0.08 IN OUT IN IN OUT IN
-0.09 IN OUT IN IN OUT OUT
-0.10 IN OUT IN OUT IN IN
-0.11 IN OUT IN OUT IN OUT
-0.12 IN OUT IN OUT OUT IN
-0.13 IN OUT IN OUT OUT OUT
-0.14 IN O UT OUT IN IN IN
-0.15 IN O UT OUT IN IN OUT
-0.16 IN OUT OUT IN OUT IN
-0.17 IN OUT OUT IN OUT OUT
-0.18 IN OUT OUT OUT IN IN
-0.19 IN OUT OUT OUT IN OUT
-0.20 IN OUT OUT OUT OUT IN
-0.21 IN OUT OUT OUT OUT OUT
-0.22 OUT IN IN IN IN IN
-0.23 OUT IN IN IN IN OUT
-0.24 OUT IN IN IN OUT IN
-0.25 OUT IN IN IN OUT OUT
-0.26 OUT IN IN OUT IN IN
-0.27 OUT IN IN OUT IN OUT
-0.28 OUT IN IN OUT OUT IN
-0.29 OUT IN IN OUT OUT OUT
-0.30 OUT IN OUT IN IN IN
-0.31 OUT IN OUT IN IN OUT
-0.32 OUT IN OUT IN OUT IN
-0.33 OUT IN OUT IN OUT OUT
-0.34 OUT IN OUT OUT IN IN
-0.35 OUT IN OUT OUT IN OUT
-0.36 OUT IN OUT OUT OUT IN
-0.37 OUT IN OUT OUT OUT OUT
-0.38OUTOUTININININ
-0.39 OUT OUT IN IN IN OUT
-0.40 OUT OUT IN IN OUT IN
-0.41 OUT OUT IN IN OUT OUT
-0.42 OUT OUT IN OUT IN IN
-0.43 OUT OUT IN OUT IN OUT
-0.44 OUT OUT IN OUT OUT IN
-0.45 OUT OUT IN OUT OUT OUT
-0.46 OUT OUT OUT IN IN IN
-0.47 OUT OUT OUT IN IN OUT
-0.48 OUT OUT OUT IN OUT IN
-0.49 OUT OUT OUT IN OUT OUT
-0.50 OUT OUT OUT OUT IN IN
-0.51 OUT OUT OUT OUT IN OUT
-0.52 OUT OUT OUT OUT OUT IN
-0.53 OUT OUT OUT OUT OUT OUT
Pressure Setpoint Table
Output
WC
DIP switch settings
DIP SWITCHES
OUT = ON (Towards You)
IN = OFF (Away from You)
8 7 6 5 4 3 2 1
6 1