I N S TA L L AT I O N & O P E R AT I O N M A N U A L Fan Filter Unit FFDE, FFDER, & FFDERA Models
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Ta b l e of Contents Critical Operations of the Fan Filter Unit .......................................................................... 3 Warnings................................................................................................................................ 4 Installation.....................................................................................................................
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Critical Operation Conditions of FFDE, FFDER, & FFDERA models 1. Touching of the HEPA filter will damage it, voiding the warranty on the filter. The screen is only to protect against an accidental ‘touch’ of the filter. Never place a hand or tool on the filte . Never lie filter face flat down on a surface alwa have filter on its side to protect from damage. 2.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Warning TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: A. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction. B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. C.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Installation Note: Titus fan filter units are completely assembled at the factory with the exception of the optional ¼”-20 eyebolts that are used when hanging the unit from an engineered design support system and installation of the HEPA/ULPA filters (eyebolts not included and can be ordered separately, p/n 222449-001). Step 1.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Unit Control Box 2.1. ON/OFF Switch - Speed/Airflow Adjustment All units are equipped with a two-position rocker switch (ON/OFF), which is located on the side of the electrical box, on top of the unit. Unless specified otherwise units are furnished with a Universal Control Card to enable adjustment of airflow or set to your means of communication. (see Page 7 for CON4 Universal Card Card Set Up).
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L CON4 Universal Control Card Set Up (Model ENV1028) CON4 UNIVERSAL CONTROL CARD - PRODUCT OVERVIEW Titus’s ENV1028 Universal Control Card provides MODBUS network and analog control capabilities to a Titus Fan Filter Unit equipped with an electrically commutated motor.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L CONTROL MODES The ENV1028 operates in one of three selectable modes. The Mode is selected using DIP Switch S1.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Manual Control Mode: In Manual control mode, the motor speed is set using the onboard potentiometer. Onboard potentiometer rotation is CW to increase the motor output. Analog Control Mode: In ANALOG control mode, the motor output is set using an external 0-10 VDC demand signal. Network Control Mode: In NETWORK control mode, the motor output is set using MODBUS Register 2.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L ELECTRICAL SPECIFICATIONS Control and Interface Signals: 1. External Speed 0-10V Input • Input impedance 20k Ohms. • MIN ON-to-OFF threshold: 190mV* • MAX OFF-to-ON threshold: 240mV* • ON (~215mV) to 9.89V linearly scales 1 to 99% speed. • 9.89V or more deadbands to 100% speed. 2. External LED Output • 10mA regulated • LED forward voltages up to 5V 3.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L COMMUNICATION SPECIFICATIONS Overview: • MODBUS RTU protocol over RS485 (serial) • 9600 baud rate, word length is 8, parity is none(n), stop bits=1 • 255 unique address values selectable by DIP switch settings • (recommended network node capacity 200 nodes) • Slew rate limited transceivers for improved network performance MODBUS Register Summary Table • DO NOT USE CROSSOVER CABLES.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Troubleshooting Mode Choice: Verify mode setting choice to DIP switch S1 (Control Mode), which is manual mode and then retry.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Infrared Speed Control (Optional) The Flow-Set is a handheld infrared remote control configured to adjust the fan filter unit. An EVO/ECM-IRC control sends the motors a FLOW INDEX and a GO signal. The motor sends back a status signal that is connected to a red lamp. The control includes an infrared remote receiver.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Cleaning the Pre-filter (foam) WARNING Tools Required: None. DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING Note: To keep the filter in top operating condition, washing ANY SERVICE the foam prefilter is recommended every three to six months. Step 1.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Service: Removal and Replacement of FFDE HEPA/ULPA Filters WARNING DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING ANY SERVICE WARNING THE STANDARD FILTER IS PROTECTED WITH AN EXTENDED METAL FACE SCEEN. THIS IS NEVER TO BE USED TO HANDLE THE FILTER. IT IS ONLY FOR PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE FILTER.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Service: Removal and Replacement of FFDER & FFDERA Filters WARNING THE STANDARD FILTER IS PROTECTED WITH AN EXTENDED METAL FACE SCEEN. THIS IS NEVER TO BE USED TO HANDLE THE FILTER. IT IS ONLY FOR PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE FILTER.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Service: FFDE and FFDER Motor Removal and Installation WARNING DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING ANY SERVICE WARNING ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED BY A LICENSED OR QUALIFIED ELECTRICIAN Tools Required: Phillips Head Driver, Battery Operated Drill, (2) 8” adjustable wrenches, 10 mm hex head wrench, #2 screwdriver, and slip joint pliers.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Service: FFDERA Motor Removal and Installation WARNING DISCONNECT THE UNIT FROM THE ELECTRICAL POWER SOURCE BEFORE ATTEMPTING ANY SERVICE WARNING ELECTRICAL SERVICE SHOULD ONLY BE PERFORMED BY A LICENSED OR QUALIFIED ELECTRICIAN Note: Minimum 2 person project.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L TECHNICAL NOTES Changing out from GE 2.3 to Nidec PerfectSpeed DC Motors in the field The Titus family of Fan Filter Units has previously used the GE 2.3 motor that was purchased by Regal Beloit. The older models have GE 2.3 motors that have become obsolete and are replaced with the new Regal Beloit model EON.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L TECHNICAL NOTES Motor Cable Configurations Installation & Operation 20
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L TECHNICAL NOTES Designs with Duct Collar, VAV or constant air box and fan coils For applications requiring powered fan filter units and a ducted connection our recommendation would be to use FFD, FFDR, or FFDRA units equipped with PSC motors. Caution FFDE, FFDER, and FFDERA units are not recommend for use with ducted systems, and cannot operate with inlet static pressure exceeding 0.30 in wg.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Wiring Diagrams 4 Pin MTA Motor Connector Remote Run Indicator LED 4 pin Control Cable 5 pin Power Cable Universal Card Wiring Diagram Installation & Operation 22
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Wiring Diagrams Infrared Speed Control Remote Mounted Visual Control Unit Installation & Operation 23
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Replacement Parts List Model FFDE FFDER FFDERA Size/Voltage N/A N/A N/A N/A N/A N/A 120V 208V-240V 277V N/A N/A N/A N/A N/A N/A FFDE FFDER 2x2 - 120V 2x2 - 208V-240V 2x2 - 277V 4x2 - 120V 4x2 - 208V-240V 4x2 - 277V FFDERA 2x2 - 120V 2x2 - 208V-240V 2x2 - 277V 4x2 - 120V 4x2 - 208V-240V 4x2 - 277V Description Disconnect Switch Pre-filter (foam) Deflector - Filter Gasket, Neop .125x.
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L FFDE Filter Drawing Installation & Operation 25
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L FFDER and FFDERA Filter Drawing Installation & Operation 26
Fan Filter Unit IOM FFDE, FFDER, FFDERA Models I N S TA L L AT I O N & O P E R AT I O N M A N U A L Testing Each fan filter unit is thoroughly tested at the factory before shipment. However, because of the “rigors” of shipping, Titus encourages units are re-tested after installation. Titus recommends that the customer contact an independent organization, with technicians trained and experienced in performance evaluation and maintenance of clean air equipment.