User manual

MODBUS RTU, ASCII, TCP 21
English
Register description
F. code
(Hex)
INTEGER
Data meaning
Register
(Hex)
Words
COUNTER & COMMUNICATION MODULE DATA
Serial number 03 / 04 0500 5 10 ASCII chars. ($00÷$FF)
Model 03 / 04 0505 1 $03=6A 3phases/4wires
$06=6A 3phases/3wires
$08=80A 3phases/4wires
$0A=80A 3phases/3wires
$0C=80A 1phase/2wires
Type 03 / 04 0506 1 $02=MID
Firmware release 03 / 04 0507 1 Convert the read Hex value in
Decimal value.
e.g. $66=102
=rel. 1.02
Hardware version 03 / 04 0508 1 Convert the read Hex value in
Decimal value.
e.g. $64=100
=rev. 1.00
Reserved 03 / 04 0509 2
Tariff in use 03 / 04 050B 1 $01=tariff 1
$02=tariff 2
Primary/secondary value 03 / 04 050C 1 $00=primary
$01=secondary
Error code 03 / 04 050D 1 $00=none
$01=phase sequence error
CT value (only for combined counter 6A 3phase model) 03 / 04 050E 1 $0001÷$2710
Reserved 03 / 04 050F 2
FSA value 03 / 04 0511 1 $00=1A
$01=5A
$02=80A
Wiring mode 03 0512 1 $01=3-phases/4 wires/3 currents
$02=3-phases/3 wires/2 currents
$03=1-phase
MODBUS address
(not available for LAN GATEWAY)
03 0513 1 $01÷$F7
MODBUS mode
(not available for LAN GATEWAY)
03 0514 1 $00=7E2 (ASCII)
$01=8N1 (RTU)
Communication speed
(not available for LAN GATEWAY)
03 0515 1 $01=300 bps
$02=600 bps
$03=1200 bps
$04=2400 bps
$05=4800 bps
$06=9600 bps
$07=19200 bps
$08=38400 bps
$09=57600 bps
$0A=115200 bps