User's Manual
TigoMaster 2TH User Manual
Page 36 of 36
CONFIDENTIAL
Copyright © 2020 CoreTigo Ltd.
6.
Technical data
Table 19 - Technical data TIGOMASTER 2TH
Category
Parameter
Value
Product
Part number
1912.122
Product name
TIGOMASTER 2TH
Description
TigoEngine EtherNet/IP IO-Link Wireless Master
Function
• IO-Link Master Wireless for EtherNet/IP
• 2 tracks, 16 channels
• Connector/housing: 30 mm
Communication
controller
Type
netX 90
Integrated memory
RAM
16 MB SDRAM
FLASH
8 MB
Ethernet
communication
Real-Time Ethernet
EtherNet/IP Adapter
Ethernet interface
Interface type
100BASE-TX, 10BASE-T, isolated
Auto-negotiation, Auto crossover
yes
Connectors
X31: Ethernet interface, M12, D-coded, EtherNet/IP port 1,
X32: Ethernet interface, M12, D-coded, EtherNet/IP port 2
IO-Link Wireless
Radio
2 track = 16 IO-Link wireless salves, 3
antennas, 16 LEDs
Output power
10dBm max.
LEDs
System and application
SYS
System status
green/
yellow
APL
Application status
red/green
Power supply
1L (X22)
1L power supply (DC 24 V)
red/green
2L (X22)
2L power supply (DC 24 V)
red/green
EtherNet/IP communication
MS
Module status
red/green
NS
Network status
red/green
Ethernet
LINK (X31)
Link status, connector X31
green
ACT (X31)
Activity status, connector X31
yellow
LINK (X32)
Link status, connector X32
green
ACT (X32)
Activity status, connector X32
yellow
Wireless tracks
WT01 ...
WT03
IO-Link wireless track status,
antenna X1 … X3
red/yellow/
green
Wireless ports
WP01 ...
WP08
Port status, IO-Link wireless
device ports P01 to P08
red/yellow/
green
WP09 ...
WP16
Port status, IO-Link wireless
device ports P09 to P16
red/yellow/
green
Power supply 1L, 2L
Voltage supply
24V DC, –25%/+30% (18 V DC … 31,2 V DC)
Under voltage warming
17.0 V (17.5 V -3%): ON,
18 V (17.5 V +3%): OFF
Over voltage warming
32.1 V (31.2 V +3%): ON,
30.3 V (31.2 V -3%): OFF
Power consumption (w/o DI/DO)
1L: 0.2 A (at 24 V DC),
2L: 0.1 A (at 24 V DC)
Connectors
X21: Power supply input (Power In), M12, L-coded, X22:
Power supply output (Power Out), M12, L-coded
Power consumption
(power connectors)
Max. 16 A,
Max. current of the device including pass through must not
exceed 16 A for 1L and 2L
Revers polarity protection
Yes