Manual
11
4. In windy areas, even a large leak can be difficult to find. Under these conditions, it is
best to shield the potential leak area from wind or breezes.
5. A leak is a constant source of refrigerant, and when a true leak source is located, it
should produce a repeatable alarm each time it is approached. Intermittent (non-
repeatable) alarms are often caused by accumulations of refrigerant near or around
leak points.
6. If an alarm occurs, and cannot be repeated when the probe tip is placed at the
same point again, it is unlikely there is a significant leak present at that point.
However, this may be indicative of a leak nearby – and can be used as a diagnostic
aid in leak finding.
SAE J1628 Recommended Procedure
NOTE: Leak test automotive A/C systems with the engine turned OFF.
1. The air conditioning or refrigeration system should be charged with sufficient
refrigerant to have gauge pressure of at least 340 kPa (50 psi) when not in
operation. At temperature below 15°C (59°F), leaks may not be measurable, since
this pressure may not be reached.
2. Do not contaminate the detector probe tip nor part being tested. If the part is
particularly dirty, or condensation (moisture) is present, clean it with a dry shop
towel or shop air. Do not use cleaners or solvents, since the detector may be
sensitive to their ingredients.
3. Visually trace the entire refrigerant system, and look for signs of air conditioning
lubricant leakage, damage, and corrosion on all lines, hoses, and components.
Check each questionable area with the detector probe, as well as fittings, hose-to-
line couplings, refrigerant controls, service ports with caps in place, brazed or
welded areas, areas around attachment points, and hold-downs on lines and
components.
4. Follow the refrigerant system around in a continuous path so no areas of potential
leaks are missed. If a leak is found, continue to test the remainder of the system.
5. At each area checked, move the probe around the location at a rate no more than
25 to 50 mm/second (1–2 inch/second), and no more than 5 mm (1/4 in.) from the
surface, and completely around the position. Slower and closer movement of the
probe greatly improves the likelihood of finding a leak (see Fig. 6). Any increase in
the alarm rate is indicative of a leak.
Fig. 6