4
Specifications
Table 1 Specifications of ventilator (heat recovery fresh air handling unit)
Ventilator (heat recovery fresh air handling unit)
Model TRV015 TRV025 TRV035
Power supply 220V~50Hz 220V~50Hz 220V~50Hz
Protection grade against
electric shock
Category I Category I Category I
IP rating IPX2 IPX2 IPX2
Item Unit Low High Low High Low High
ESP Pa 80 80 80 80 80 80
Air flow m³/h 100 150 160 250 180 350
Heat
recovery
efficiency
Enthalpy
efficiency of
cooling
%
55 52 51
Temperature
efficiency of
cooling
67 63 62
Enthalpy
efficiency of
heating
75 72 68
Temperature
efficiency of
heating
85 82 80
Power W 105 148 276
PM2.5 primary purification
efficiency
% 95 95 95
Noise dB (A) 32 34 39
Net weight kg 24 24 27