ODU Control Panel
Settings of relevant keys
1. Contents to be set
(1) SP03: setting of addresses of equipment for centralized monitoring;
(2) SP04: setting of centralized monitoring of baud rate;
(3) SP05: setting of models (TIMS-S/ST/SA/SRYA models and TIMS-X/XA models)
(4) SP06: fan operating mode (auto quiet mode, smart quiet mode, and forced quiet
mode);
(5) SP07: compressor drive (hardware) configuration;
(6) SP08: fan drive (hardware) configuration;
(7) SP09: compressor model configuration;
(8) SP10: fan model configuration.
2 Buttons and corresponding labels
Buttons: KEY1, KEY2, KEY3, KEY4, KEY5.
Shown icons:
(1) dP04 : Parameter setting function No.
(2) SP** : indicates parameter number, where ** indicates specific parameter number (01,
02……07, 08).
(3) Ar**: indicates addresses of equipment for centralized monitoring, where ** indicates
specific address (01, 02…… 07, 08).
(4) b*** : indicates centralized baud rate, where *** indicates specific address (12, 24, 48,
96, 192), which is corresponding to the baud rate of 1200, 2400, 4800, 9600 and 19200
respectively.
(5) Sn** : Sn00: indicates TIMS-S/ST/SA/SRYA models; Sn01: indicates TIMS-X/XA
models.
(6) qoFF : close fan mode selection; auto-quiet mode
qon2: smart quiet mode; qon3: forced quiet mode.