Installation Guide
Table Of Contents
31
TIMS260-S
TIMS260-SA
418/342 80
25mm
2
≤20 25mm
2
35mm
2
20-50 35mm
2
ODU model Power supply
Voltage
range (V)
Wiring
current (A)
General
power cord
Length
(m)
GND
Communication
line
TIMS280-S
TIMS280-SA
3N/380V
/50Hz
418/342 80
25mm
2
≤20 25mm
2
0.75-1.25 mm
2
polyethylene
shielded twisted
pair
35mm
2
20~50 35mm
2
TIMS300-S
TIMS300-SA
418/342 80
25mm
2
≤20 25mm
2
35mm
2
20-50 35mm
2
TIMS320-S
TIMS320-SA
418/342 80
25mm
2
≤20 25mm
2
35mm
2
20-50 35mm
2
TIMS340-SA 418/342 80
25mm
2
≤20 25mm
2
35mm
2
20-50 35mm
2
Electric Control Installation
Electrical wiring
Power supply
Earth line cannot be connected to
neutral line
On/Off
Fuse
On/Off
Fuse
On/Off
Fuse
IDU 1
IDU 2
IDU i
Communication wiring