Electric Control Installation
Wiring specifications
Notes:
● As wires need to be bent during installation process, it is recommended to use
flexible wires, otherwise installation may fail.
● The parameters in the table below are corresponding to multiple strands of flexible
copper wires. If other wires are selected, please refer to electrician's manual based
on wiring current provided in the table.
● For safety purpose, do not carry out wiring work based on rated current, for the
operating conditions may be varied with seasons.
Table of ODU wiring specification
ODU model Power supply
Voltage
range (V)
Wiring
current (A)
General
power cord
Length
(m)
GND
Communication
line
TIMS080-S
TIMS080-ST
TIMS252CSRYA
3N/380V
/50Hz
418/342 20
6mm
2
≤20 6mm
2
0.75-1.25 mm
2
polyethylene
shielded twisted
pair
10mm
2
20-50 10mm
2
TIMS100-S
TIMS100-ST
TIMS285CSRYA
418/342 25
6mm
2
≤20 6mm
2
10mm
2
20-50 10mm
2
TIMS120-S
TIMS120-ST
TIMS335CSRYA
418/342 32
6mm
2
≤20 6mm
2
10mm
2
20~50 10mm
2
TIMS140-S
TIMS140-ST
TIMS400CSRYA
418/342 40
10mm
2
≤20 10mm
2
16mm
2
20~50 16mm
2
TIMS160-S
TIMS160-ST
TIMS450CSRYA
418/342 40
10mm
2
≤20 10mm
2
16mm
2
20 〜 50
16mm
2
TIMS180-ST
418/342 50
10mm
2
≤20 10mm
2
16mm
2
20~50 16mm
2
TIMS180-S
TIMS200-S
TIMS200-ST
TIMS200-SA
418/342 50
16mm
2
≤20 16mm
2
25mm
2
20~50 25mm
2
TIMS220-S
TIMS220-ST
TIMS220-SA
418/342 63
16mm
2
≤20 16mm
2
25mm
2
20~50 25mm
2
TIMS240-S
TIMS240-SA
418/342 63
16mm
2
≤20 16mm
2
25mm
2
20~50 25mm
2