Installation Guide

25
Installation of Refrigerant
Piping
Refrigerant piping length
Capacity combination
50% ≤
ΣRated cooling capacity of IDU
Rated cooling capacity of ODU
≤ 130%
Remarks: It is recommended that the above value shall not be greater than 100% when
selecting models. For scenarios with lower simultaneous usage coefficient, the above value
may exceed 100%.
Unit capacity Single module
Maximum equivalent piping length ≤ 400 m
Level
difference
Level difference
between IDU and ODU
H1 ≤ 50 m (when the ODU is at the upper position)
H1 ≤ 40 m (when the ODU is at the lower position)
Level difference among
IDUs
H2 ≤ 30 m
Note (1): Equivalent length is the converted length after taking into account of pressure
losses at elbows.
Equivalent length = actual pipe length + number of elbows x equivalent length of
each elbow
Equivalent length of every place of branch pipe is 0.5 m, and please refer to the
following table for equivalent length of elbows.
Pipe diameter
Equivalent length
Elbow (m)
Φ9.52
0.18
Φ12.7 0.2
Φ15.88 0.25
Φ19.05 0.35
Φ22.23 0.4
Φ25.4
0.45
Φ28.6 0.5
Φ31.8 0.55
Φ34.9 0.6
Φ38.1 0.65
Φ41.3
0.7
Precautions when breaking through the knockout
Do not damage the unit shell when trying to break through the knockout.
Smooth the burrs around the hole and apply anti-rust paint after opening the
knockout with a mallet or other tools.
When passing the wire through knockout, put grommet in the hole or wrap wires with
adhesive tape for protection.