Installation of ODU
Handling
Notes:
● Fragile and handle with care.
● The degree of inclination shall not exceed 30° while handling (do not put the unit on
its side).
● Keep heat exchange fins safe while handling and installing the unit. In case of any
damages, please use fin comb to fix it up.
● Properly dispose of packaging bags and prevent kids from playing with them.
Hoo k
Hoi sting rop e
Prot ective pa d
Lift in g hole (two at the front
an d two at th e b ack )
Ke ep th e r op es t hr ou gh th e
ho les t o ensu re sta bil it y
during hoisting.
Forklift pocket
● Use forklift to handle: be careful when inserting the fork into the pocket at the bottom,
and prevent fork from damaging the unit or the unit bottom.
● Use crane to handle: tighten hoisting rope according to what is shown in the figure,
and keep the unit weight even during hoisting.
● Use two hoisting ropes at least 8 m long and about 20 mm in diameter to support the
unit weight. Do not use tying band of the unit for handling.
● After the wooden framework is removed: use paper or cloth as pad between hoisting
rope and the unit to prevent damages to the unit body.
Placement
● Make sure the ODU is placed firmly at a level place to prevent vibration and noises.
● Use a base larger than the width of ODU's support legs (66 mm) to support the unit.
● The shock-absorbing pads shall cover the entire bearing surface of the base.
● The unit base shall be at least 200 mm higher above the ground.
● Around the base there should be drain to ensure that the condensate water
generated during operation could flow out.