Installation Manual
Table Of Contents
J- SAP -TC SB5406W Wireless Digital Manual Call Point
Installation making use instructions Ver1.1 202011
YINGKOU TIANCHENG FIRE PROTECTION EQUIPMENT CO., LTD
2
2.2 Adopting 470MHz wireless communication technology , without pre-buried wiring, convenient and
quick engineering installation;
2.3 With battery low voltage detection function , it can reflect the battery power situation in time;
2.4 The use of microprocessor to realize signal processing and digital signal to communicate with the
control panel, the work is stable and reliable, and has a good ability to suppress electromagnetic
interference.
3.Technical characteristic
3.1 . Battery Type: CR17450 3.0 V / 2400mAh Voltage range: 2 .7 ~ 3.3 V
3.2 . Operating Current: Monitor current ≤ 10 uA alarm current ≤ .19 m A
3.3 . Indicator:
Fire light: red, not network when logging every 48s flash time, alarm always lightens
Fault light: yellow , flashes twice every 48s when the battery is under power, and periodically
flashes when the communication fails after being connected to the network
Working light: green , flashing periodically when the communication is normal after entering the
network
3.4 . Encoding: automatically allocated when the network control panel
3.5 . Communication: 470MHz FSK encoded two-way communication
3.6 . Communication distance: ≤50m
3.7. Transmitting power: <20dBm
3.8 . Reset: special key reset
3.9. Form of starting parts: reusable type
3.10 . Use of the environment:
Type: Indoor atmospheric pressure: 86kPa~106kPa
Temperature: -10℃~+55℃ Relative humidity ≤95%, non-condensing
3.11 . Dimensions: 95 m m × 96 m m × 50 m m
3.12 . Shell materials and colors: the ABS , red color
3.13 . Weight: about . 19 0 G (with battery)
3.14 . Implementation of the standards:
GB 19880-2005 "manual fire alarm button "
XF 1151-2014 " General Requirements for Wireless Communication Function of Fire Alarm
System "
4.Structural features and working principle
4.1 . Alarm button contour diagram shown in Figure 1 below: