User's Manual

JTY-GM-TC5401WWireless Addressable Photoelectric Smoke Detector User Manual Ver1.0 202010
Yingkou Tiancheng Fire Protection Equipment Co., LTD
6
VIII.General Fault and Solutions
The general faults and solutions are shown in the following table:
Fault
Reason
Solution
No status prompt on the control panel
after device alarms
The device is not connected to the
network
Restart the network operation
Device networking is unsuccessful
Too far away from the control panel
or interference sources nearby
Move the device near the controller,
reconnect to the network and remove
the source of interference
Red light is off
Low battery or no battery inserted
Replace battery
IX. Maintenance
1. The detector should take corresponding moisture-proof and anti-corrosion measures.
2. The detector is cleaned at least once a year to ensure the normal operation of the system. Before the detector is cleaned,
the relevant management department should be notified that the system will be maintained, and the logical control
function of the area or the system that will be maintained should be closed to avoid unnecessary alarm linkage.
3. The detector should conduct a simulated fire alarm test every six months to test whether the detector works normally.
X.Notes
1. The horizontal distance between the detector and the air supply hole of the air conditioner should not be less than
1.5m.
2. The horizontal distance from the detector to the wall and beam side should not be less than 0.5m.
3. The detector should be installed horizontally. If it must be installed at an angle, the inclination angle should not be
greater than 45°.
4. In places where smoldering fire may occur, smoke detectors should not be used.
5. When installing detectors on the ceiling of the inner walkway with a width less than 3m, they should be arranged in the
center, and the installation distance of smoke detectors should not exceed 10m.
6. After the signal passes through the wall, the signal strength will be greatly attenuated, so try to reduce the number of
partition walls for wireless products.
7. When installing the product, keep it away from metal to reduce the shielding of the signal from metal objects. For
example, it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet.
8. Install in a low-interference environment and far away from motors or large-scale electrical equipment.
XI. Documents and warranty
1. Packing documents:
1) Packing list: 1
2) Instructions: 1 copy