User's Manual
Table Of Contents
- I. General
- II. Main Characteristics
- III. Technical Specifications
- IV. Structure and Working Principle
- 1. Points for on-site installation
- The wireless performance indicators of this produc
- VI. Test
- 1. The detector must be tested after installation
- 2. Simulated fire alarm: After the networking is s
- 3. In the process of testing, the unqualified dete
- VII. Use and Operation
- 1.Network segment setting: Before the detector con
- 2. Device enters and exits the network: After the
- A) Network access: When the control panel is in th
- B) Network exit operation: When the control panel
- 3. Equipment alarm:
- When the smoke concentration in the environment re
- 4. Device reset: When the device reports a fire al
- 5. Restore factory settings: After the detector is
- Note: The button function only has one click, thre
- VIII.General Fault and Solutions
- IX. Maintenance
JTY-GM-TC5401WWireless Addressable Photoelectric Smoke Detector User Manual Ver1.0 202010
Yingkou Tiancheng Fire Protection Equipment Co., LTD
5
VI. Test
1. The detector must be tested after installation or after each regular maintenance.
2. Simulated fire alarm: After the networking is successful, choose a detector to artificially make it meet the fire alarm
conditions (please turn off the fire alarm linkage function to avoid unnecessary alarm linkage), and verify whether the
detector reports the fire alarm normally. After the test is over, the detector is reset by operating the control panel reset,
and the system returns to the normal monitoring state.
3. In the process of testing, the unqualified detector shall be dealt with according to "General failure and repair" and
"Maintenance", and then test again. If it still fails to pass the test, it should be returned to the factory for repair.
VII. Use and Operation
1.Network segment setting: Before the detector connects to the network, you should first set the device network segment.
Select the network setting on the menu interface of the controller. After entering the network setting, first set the local
address number, and then set the detector to connect to the network according to the actual situation on site. (Segments:
29 options).
2. Device enters and exits the network: After the detector is powered on, press the "Indicators" button once, the green
light flashes once, the detector sends an online command to the control panel, and the the control panel displays the loop
address number of the detector, indicating that the detector has successfully connected to the network. Otherwise the
detector is not connected to the network. The detector sends online commands for 3s, during which other functions of the
keys are disabled. The detector does not send online commands, and the red light does not flash.
A) Network access: When the control panel is in the "Wireless registration interface" and the detector is not connected to
the network, quickly press the "Indicators" button three times, the green light flashes three times, the detector sends a
network access application to the control panel, and the application is successful. After that, the total number of network
access displayed by the control panel is +1, and the detector sends a network access request for 3 seconds. During this
period, other functions of the button are disabled.
B) Network exit operation: When the control panel is in the "Wireless registration interface" and the detector is in the
network connection state, quickly press the "Indicators" button three times, the green light flashes three times, and the
detector sends an exit request to the controller. After the application is successful, the total number of logouts displayed
by the controller is +1, and the detector sends a logout request for 3s. During this period, other functions of the button are
disabled.
3. Equipment alarm:
When the smoke concentration in the environment reaches or exceeds the alarm concentration set by the detector, the
red light of the detector is always on, and an alarm signal is sent wirelessly to the control panel. After the controller
responds to the alarm signal, the control panel displays a fire alarm and the detector is in Waiting for the control panel
reset state, after confirming that the fire alarm is released, the control panel can send a signal to reset the detector.
4. Device reset: When the device reports a fire alarm and the control panel responds, it can be reset by operating the
control panel. After the detector receives the reset signal, it will perform the reset operation.
5. Restore factory settings: After the detector is connected to the network, when it is powered on again, the red indicators
will be on for 10s; during this period, the factory settings can be restored by pressing the button five times.
Note: The button function only has one click, three consecutive clicks, five consecutive clicks, long press function, and
other button methods are invalid.