User's Manual

JTY-GM-TC5401WWireless Addressable Photoelectric Smoke Detector User Manual Ver1.0 202010
Yingkou Tiancheng Fire Protection Equipment Co., LTD
2
II. Main Characteristics
1.Using advanced wireless communication technology, signal transmission can be completed without wiring, and the
engineering installation is simple and convenient;
2.Using 470MHz frequency band communication, FSK coding technology, strong anti-interference ability, long transmission
distance;
3.With battery low-voltage detection function, remind users to replace when the battery is insufficient to maintain the
detector's normal operation.
4.With dust accumulation alarm function.
III. Technical Specifications
1. Battery model: CR17450 3V
2. Working Current: Standby Current8uA; Alarm Current18mA
3. Indicators: Fire Indicator: red, flashing once every 48s during inspection, and always on when alarming
Fault Indicator: yellow, flashes twice every 48s when the battery is under power, and periodically flashes when the
communication fails after being connected to the network
Working Indicator: Green, flashing periodically when the communication is normal after entering the network
4. Coding method: automatically assigned by the controller during networking
5. Communication method: 470MHz FSK coded two-way communication
6. Communication distance: 50m
7. Transmitting power: <20dBm
8. Frequency band: 470MHz
9. Protection area: When the height of the space is less than 8m, the protection area of a detector is 2030 for the
general protection site.
The specific parameters should be based on the "Code for Design of Automatic Fire Alarm System" (GB 50116-2013).
10. Use environment: Atmospheric pressure: 86kPa106kPa
Temperature: -10℃~+55
Relative humidity: 95%, no condensation
11. Dimensions: diameter 100mm high 55mm (including base)
12. Shell protection grade: IP30
13. Shell material and color: ABS, off-white
14. Weight: about 118g (including battery)
15. Installation hole distance: 60mm
16. Executive standard: GB 4715-2005 "Point Type Smoke Fire Detector"
XF 1151-2014 "General Requirements for Wireless Communication Function of Fire Alarm System"