Installation Instructions
history, fault history and other history each have a capacity of 1000. It CAN support
CAN bus and network with other fire alarm control panels of our company. Wireless
470MHZ communication mode is adopted to connect with the detectors matched with
the system. Executive standard: GB4717-2005 fire alarm control panel GA 1151-2014
general requirements for wireless communication function of fire alarm system
GB16806-2006 fire linkage control system
1.3 Introduction of control panel components
In order to make you more familiar with the control panel, the following briefly
introduces the main components of the control panel:
·Main control module
The main control board is responsible for analyzing and processing the information
data transmitted by other components in the system, and according to the data analysis
results, commanding other components in the system to execute corresponding
commands, such as control speaker voice alarm, etc.
·Display module
The display component provides the main output interface of alarm information, as
well as the daily maintenance and query interface.
·Key module
Matrix buttons are used in the control panel, which is very convenient for users to set
up and maintain the system.
·Power module
The power supply module supplies power for the whole system equipment, and
provides power fault signals such as main power fault, standby power fault and
standby power undervoltage, and has good anti-interference ability.
·Wireless 470 module
The 470MHzFSK coded bidirectional communication can communicate with 32
wireless devices.
·Loop control panel
This control panel can be connected with 18 intelligent loop control panels, which has
less wiring and high reliability. Each start/stop key on the manual fire control startup
panel can be associated with any bus equipment connected to the system by definition,
and complete the start/stop control of the bus linkage equipment, thus thoroughly
solving the inherent problems of engineering wiring, equipment configuration and
installation and debugging of the alarm linkage integrated system.
·Direct control panel
This control panel can be equipped with 6-way three-wire direct control panel, and
has the functions of detecting open circuit and short circuit of output line, which can
guarantee the reliability of the control module itself and its connection with important
equipment to the maximum extent.
1.4 Main technical specifications
1.4.1 power supply
Main power supply: AC 220V (3.5A) voltage range+10% ~-15%.