Installation Instructions

Appendix I Technical Indicators
Control panel capacity:
Up to 2 wireless circuits with 32 address points per circuit.
Up to 1 multi-wire control panel, 6 groups in total.
Up to 1 bus control panel, 18 groups in total.
Wiring system:
Wiring system
Circuit
Distance
Quantity and use
RS485bus
two-core disable
wire
< 500m
1 CRT
Multi-loop
control line
(three-loop
system)
≥1.0mm
2 RV
conductor
< 1.5km
6 points per control
panel
Temperature:-10 ~+55
Relative humidity 95%, non-condensing
Power supply:
Main power: AC 220V (3.5A) voltage variation range+10% ~-15%
Backup power: DC 24V(3.3A), backup battery: 2 sealed lead-acid batteries of
12V/3.3AH