Installation Instructions

If this method is used, the network segments are not enough and can be recycled.
Ensure that the network segments between adjacent control panels are separated by
more than 5 network segments, and the greater the interval, the smaller the mutual
interference. Then enter the registration, and press the "Up and Down" button to select
the sensitivity for sensing equipment.
5.5 Editing method of automatic linkage formula
on-site equipment mainly refers to the equipment connected to the control panel, each
of which occupies one coding point. The system provides up to two wireless circuits,
and each circuit has 32 coding points. These devices include fire detectors (such as
temperature detectors with differential temperature and photoelectric smoke detectors),
input modules, fire hydrants, input and output modules, etc.
5.6.1 Format of linkage formula
The linkage formula is a logical expression used to define the linkage relationship
between alarm equipment and controlled equipment in the system. When the detection
equipment in the system alarms or the state of the control module changes, the control
panel can automatically start or stop the controlled equipment according to these
logical expressions. The linkage formula of this system is divided into two parts by
equal sign, followed by condition, which is composed of user code, equipment type
and relational operator The front is the equipment to be linked, which is composed of
user code and equipment type.
There are six fixed formats as follows:
1
Y(01010001 011)=(01010101 004+01020*** 004)_2
2
Y(01010001 011)=(01010*** 004)_2+(01010*** 004)_2
3
Y(01010001 011)=(01010*** 004)_1X(01010*** 004)_9
4
Y(01010001 011)=X(01010*** 004+01020*** 004)_2
5
Y(01010001 011)=X(01010*** 004)_1+(01010*** 004)_9
6
Y(01010001 011)=X(01010*** 004)_1X(01010*** 004)_9
Example: y (01010001 011) = (01010 * * * 004+01010 * * * 004) _ 2
It means: in the manual report where the first five digits of the secondary code are
01010, when any two alarms occur, No.01010001 audible and visual alarm will start
immediately.
Note:
1) symbol "=" means to start the equipment when conditions are met, symbol "= x"
means to stop the equipment when conditions are met,
2) The equipment before and after "=" in linkage formula is required to be composed
of secondary codes and equipment types, and the types cannot be defaulted. The
secondary codes and equipment types are separated by spaces. The secondary codes
and types of linkage equipment are before "=", and the secondary codes and types of
alarm equipment are after "=". The _ * after brackets in each group of alarm
equipment indicates the number of alarms that the alarm equipment meets the
conditions in brackets.
3) There are two relational symbols: "AND" and "OR", in which "+"stands for "OR"
and "X" stands for "AND".