Installation Instructions

Figure 4-3
4.4 Real-time information display and history record information display
4.4.1 Information display
When any information such as fire alarm, linkage, supervision, fault and others exists
in the system, the system will display this information; If there is more than one
information in the system, the system will display it according to the priority of fire
alarm > linkage > supervision > fault > isolation.
Figure 4-4
Figure 4-4 shows the display page of fire alarm and linkage information.
4.5 Mute
In case of fire alarm or fault, the speaker of the control panel will send out
corresponding alarm sound to prompt. Press the "mute" key, the mute indicator lights
up, and the speaker stops giving an alarm. If a new alarm occurs, the silencing
indicator goes out and the alarm sounds again.
4.6 fire alarm and fault handling
4.6.1 General handling methods of fire alarm
In case of fire alarm, first check the place where the fire alarm occurs and confirm