User's Manual
12
Timer5: START disabled, STOP: 12:00AM, REPETITION DOM: 8
This set of timers used together will turn the relay on every 1
st
of the month at 12:00AM and turn it off
7 days later on the 8
th
of the month at 12:00AM.
Configuration. The following parameters can be configured using the PowerMon app:
Initial Power Status: The default power status when powering the device. If set to on the relay will be turned on
automatically when the device receives power.
Trigger on RELAY: If enabled, the device will turn the power on as a response to the RELAY terminal being
temporarily pulled to ground using a push button.
Invert RELAY Logic: Enabling this option will invert the behavior of the RELAY terminal, when the power is on
the RELAY terminal will be floating and when the power if off it will be driven to ground.
Connect Filter (ms): The duration of time in milli-seconds the LVD (Low Voltage Disconnect), HVD and OCD (Over-
Current Disconnect) conditions have to be removed in order to re-engage the power relay.
MF Terminal Function: Selects the function of the MF terminal: Data Output or External Temperature Sensor.
The external temperature sensors is only available for hardware revision 2.2 or higher.
Device History: Configure the history sample rate. Possible values are: disabled, every second, 2 seconds, 5 sec,
10 sec, 20 sec, 30 sec or 1 minute.
Low Voltage Disconnect
LVD Connect Threshold: The voltage in volts above which the power relay can re-engage (after the
connect filter time has passed). This must be higher than LVD Disconnect Threshold.
LVD Disconnect Threshold: The voltage in volts below which the power relay will disengage.
LVD Filter (ms): The duration of time the voltage has to be below the disconnect threshold for the relay
to disengage.
High Voltage Disconnect
HVD Connect Threshold: The voltage in volts below which the power relay can re-engage (after the
connect filter time has passed). This must be lower than HVD Disconnect Threshold
HVD Disconnect Threshold: The voltage in volts above which the power relay will disengage.
HVD Filter (ms): The duration of time the voltage has to be above the disconnect threshold for the relay
to disengage.