Owner Manual
14
Gas Supply Requirement
Installation of this range must conform with local codes, or in the absence of local codes, with national
Fuel Gas Code,ANSIZ223.1 / NFPA 54. In Canada, installation must conform to the current natural Gas
Installation /code, CAN 1-1.1-M81 and with local codes where applicable. This range has been
design-certified according to ANSIZ21.1a, latest edition.
MAXIMUM GAS SUPPLY PRESSURE TO APPLIANCE FOR LP GAS---13.0 IN.W.C.
MAXIMUM GAS SUPPLY PRESSURE TO APPLIANCE FOR NG GAS---10.0 IN.W.C.
APPLIANCE REGULATOR IS SET AT 10.0IN.W.C. OUTLET PRESSURE FOR LP.
APPLIANCE REGULATOR IS SET AT 5.0IN.W.C. OUTLET PRESSURE FOR NG.
Keep appliance area clear and free from combustible materials, gasoline, and other flammable vapors.
Do not obstruct the flow of combustion air into the range and ventilation air away from the range.
Ventilation: it is recommended that the unit be set under a powered, vented exhaust hood of sufficient
size and capacity.
Before installing the range, you must locate and secure the included anti-tip bracket to the wall for your
range.
Causion: The use of cabinets for storage above the appliance may result in a potential burn hazard.
Combustible items may ignite; metallic items may become hot and cause burns. If a cabinet storage is to
be provided, the risk can be reduced by installing a range hood that projects horizontally a minimum of
5" (12.7cm) beyond the bottom of the cabinets.
Connect Range to Gas Supply
1. Install a manual gas line shut-off valve in the gas line in an easily accessed location outside the range
in the gas piping external to the appliance for the purpose of turning on or shutting off gas to the
appliance.
2. Install male
1
/
2
inch flare union adapter to
1
/
2
inch NPT internal thread elbow at inlet of regulator.
On models equipped with standard twin burners, install the male pipe thread end of the
1
/
2
inch flare
union adapter to the
1
/
2
inch NPT internal thread at inlet of pressure regulator. Use a wrench on the
regulator fitting to avoid damage.
3. Install male
1
/
2
inch or
3
/
4
inch flare union adapter to the NPT internal thread of the manual shut-off
valve, taking care to secure the shut-off valve to keep it from turning.
4. The gas supply pressure for checking the regulator setting is 6 in.w.c. (Nature Gas) and 11 inch.w.c.
(LP gas) connect flexible gas line connector to the regulator on the range. Position range to permit
connection at the shut-off valve.
When all connections have been made, make sure all range controls are in the position and turn on
main gas supply valve.
5. Leak testing of the appliance shall be conducted according to the manufacture’s instructions. Use
some soap water (50% water and 50% soap) or a leak detector at all joints and connections to check for