User's Manual Part 3

CAR4010T & 4030T
4000 Watt Single Output Rectifier Modules
97MS2101
Rev. B - 03.15.04
Cherokee International
Headquarters
2841 Dow Avenue, Tustin CA. 92780 - USA
714.544.6665 (t)
714.838.4742 (f)
www.cherokeepwr.com
Cherokee International
European Operations
Boulevard de l'Europe, 131
B-1301 Wavre - Belgium
+32.10.438.510 (t)
+32.10.438.213 (f)
CAR4010T & 4030T
Hot-Swap N+1 Redundancy
Single phase or Three phase Input
Power Factor Correction
Over Voltage, Over Current and Thermal Protection.
Visual LED Indicators
19” 3U high rack available
Specifications CAR 4010T & 4030T
Input Voltage Range CAR4010T: 180-264VAC, 47-63Hz 1Ø / CAR4030T: 180-264VAC, 47-63Hz 3Ø
Input Current (maximum) 25.5A @ Full Load and 180VAC, 1Ø and 15A per phase @ Full Load and 180VAC, 3Ø
Inrush Current 50A max
Input Fuse 30A 3AG, Internal Axial Type for 1Ø and 20A 3AG, Internal Axial Type for 3Ø
Input Transient Protection MOV and Gas tube
Power Factor 0.99 (for CAR4010T) and 0.95 (for CAR4030T) at full load and nominal line
Efficiency 89% typical at 230VAC
Output Configuration V1 V2 Standby Output
CAR4010L1TN/CAR4030L1TN -54V @ 74A 5V @0.5A
CAR4010K1T/CAR4030K1T 27V @ 148A 5V @ 0.5A
Output Voltage Range - 40 to -58V (for CAR4010L1T) and 20 to 29V (for CAR4010K1T) with external programming
Line Regulation 0.5% using remote sense (5% on Stand-by Voltage)
Load Regulation 0.5% using remote sense (5% on Stand-by Voltage)
Output Ripple & Noise <1% (pk-pk)
Transient Response 3% max deviation 0.50ms recovery time for a 25% load change
Start-up Time 2 seconds
Hold-up Time >20ms at low line
Overshoot / Undershoot 1% at turn ON / OFF
Temperature Coefficient 0.02% per °C
Remote ON / OFF Logic 1 (TTL High) or open enables unit (ON), Logic 0 (TTL Low) or short shuts unit down (OFF)
Power Fail Signal Signal goes low (TTL low) 2ms before loss of output regulation
Current Limit Protection 110-140% V1, 5VSB <2.5A. Automatic recovery.
Over Voltage Protection - 58.5 to -59.5V (for CAR4010L1TN) and 29.5 to 30.5V (for CAR4010K1T). Reset by cycling input power.
Over Temperature Protection Automatic shutdown with auto recovery. Thermal shutdown point @ 95°C
MTBF 300,000 hrs per Bellcore standard
Output Power Good TTL High = Power Good, TTL Low = Output out of limits
LED Indicators DC Good: Green LED; Temperature OK: Green LED; and AC Good: Amber LED
Operating Temperature 0°C to 50°C at rated output power. Supply derates linearly from 50°C to 65°C at 2.2% per °C
Cooling Self contained ball bearing fan.
Shock & Vibration NEBS Compliant to IEC68-2-27 & MIL-STD-810E, Telcordia GR-63-CORE; GR-487-CORE
EMI/EMC Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-Core
Safety Approvals UL1950, CSA 22.2 No. 650, TUV EN60950 & CE Mark
Weight 13.5 pounds
Features Benefits
No minimum load requirements
Eliminates the need for preload on system backplane
Modular design
Easy insertion and extraction during hot swap
Single phase or three phase inputs
One stop shopping, breadth of line for 24V and 48V outputs
Constant power characteristic
Better suited for battery charging applications
Key Market Segments & Applications
Telecommunications
Wireless/Cellular
PCS Installations
Central Office Switching
Bulk power front ends for distributed power architecture