Cut Sheet

MALE FEMALE
LOUVERED
CONTACT BANDS
Thomas & Betts Corp.
TIE 1
TIE 2
MDBOOT-0
MDBOOT-1
MDBOOT-2
MDBOOT-3
MDBOOT-4
LINE LEAD
MOTOR LEAD
A
TIE 1
TIE 2
1/4"
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
WARNING
NOT FOR DISCONNECTING ENERGIZED CIRCUITS.
16-14
12-10
8
6
4
2
1
1/0
2/0
3/0
4/0
*4/0
250 kcmil
350 kcmil
500 kcmil
WIRE SIZE
AWG
3/8
3/8
7/16
1/2
1/2
17/32
9/16
9/16
5/8
11/16
3/4
1
1-1/8
1-1/8
1-5/16
WIRE STRIP
LENGTH
A ±1/32
Sealant available, Catalog Number
MDBOOT-SEAL
#16-14
#16-14
#12-10
#8
#6
#12-10
#8
#6
#4
#2
#1
#6
#2
#1
#1/0
#2/0
#3/0
#4/0
#4/0
#250 kcmil
#350 kcmil
#500 kcmil
MD1614F-0
MD1614F-1
MD1210F-1
MD8F-1
MD6F-1
MD1210F-2
MD8F-2
MD6F-2
MD4F-2
MD2F-2
MD1F-2
MD6F-3
MD2F-3
MD1F-3
MD10F-3
MD20F-3
MD30F-3
MD40F-3
MD40F-4
MD250F-4
MD350F-4
MD500F-4
FEMALE
WIRE SIZE
AWG
MD1614M-0
MD1614M-1
MD1210M-1
MD8M-1
MD6M-1
MD1210M-2
MD8M-2
MD6M-2
MD4M-2
MD2M-2
MD1M-2
MD6M-3
MD2M-3
MD1M-3
MD10M-3
MD20M-3
MD30M-3
MD40M-3
MD40M-4
MD250M-4
MD350M-4
MD500M-4
MALE
MDBOOT-0
TY24M (2)
MDBOOT-1
TY24M (2)
MDBOOT-2
TY24M (2)
MDBOOT-3
TY242M (2)
MDBOOT-4
TYHT28M (2)
CATALOG NUMBERS
BOOT NO.
&
CABLE TIE
*Body Size -4
140B
MOTOR DISCONNECTS
INSTALLATION INSTRUCTIONS
High Conductivity Copper Color-Coded to match Installing Die.
• Flame Retardant
Formulation
Abrasion Resistant
RATM600
90°C (Body Sizes
-0, -1, -2, -3)
•125°C (Body Size -4)
CAUTION
CHECK MOTOR ROTATION BY BUMPING MOTOR.
CORRECT ROTATION IF NECESSARY.
— INSTALLATION HINTS —
A. Always install the female lug on line leads and the male lug on the
motor leads for 600V and less, female on both line leads and motor
leads for the 5KV connection.
B. Always use the smallest body size for the lug possible for the
largest wire in the junction box. Line leads are usually the largest.
C. Store the boots and bolts from the junction box in the re-closeable
plastic bag provided. Use a Ty-Rap
®
cable tie or tape the bag to the
conduit.
TA00220 T Page 1 of 2
D. IMPORTANT: After fully inserting the male pin into the female barrel
on the 600V connectors or inserting the double male pin between the
two female connectors on the 5KV connections, make sure you install
the boot that matches the size and voltage for your application.
E. IMPORTANT: properly seat connectors by fully inserting motor
connectors to the bottom of the boot. On the 600V connectors, install
the rst tie just under the connectors seated in the boot. The second tie
should be installed between the rst tie and bottom of the boot.
INSTALLATION INSTRUCTIONS
STEP 1
Select connectors as needed for
motor and line wire sizes. Be sure
to specify connectors within the
suitable size groups. Size groups
may not be inter-mated.
Connectors within each group
may be mated. (MD1210F-2
mated with MD2M-2).
STEP 2
D
ress the wires to pigtail with the
motor leads.
STEP 3
C
rimp connectors with any T&B
installing tool as follows:
WT2000, WT1300, WT130A
Installs #16 through #10
*TBM20S installs #8 to #2
TBM5, TBM5S, TBM6, TBM6S,
TBM8, TBM8S, TBM62BSCR,
TBM25S, &TBM6BSCR
*Requires (2) crimps
STEP 4
P
ush male pin into female barrel
until fully inserted.
STEP 5
S
lide insulator onto pigtailed
connectors until it stops.
STEP 6
Fasten
the rst tie at the middle
of insulator, tightening snugly.
Fasten the second tie 1/4" from
end of boot as shown, and
tighten. Cut excess tie.
STEP 7
D
ress lead assemblies into
junction box.