Limitorque MX Device Net Field Unit User's Instruction
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
24
Table 4.25
DO_ESD_ Poll_Cnxn
Attribute 21
Ctrl_Status_Chan
Attribute 20
Bit 2
DO_ESD_
Bit_Strobe_Cnxn
Attribute 22
Enable_Broadcast_
ESD_Ctrl
Attribute 23
DO_ESD_ Chan
X 0 X 0 0
0 1 X 0 0
1 1 X 0 1
X 0 0 1 0
X 0 1 1 1
1 1 1 1 1
0 1 0 1 0
0 1 1 1 1
1 1 0 1 1
4.2.10 DO_Relay_Chan
Table 4.26 Available with Revision 1 to DeviceNet board
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved User Output
AR-3
User Output
AR-2
User Output
AR-1
User Output
AS-4
User Output
AS-3
User Output
AS-2
User Output
AS-1
4.2.11 DI_Actuator_Faults_3_Chan
Available with Revision 1 to DeviceNet board.
Table 4.27
Bit 7 – Bit 4 Bit 6 Bit 5 Bit 4 Bit 3
Reserved Reserved Interboard Power
failure
Interboard
Communications
Failure
Reserved
4.2.12 Ctrl_Status_Chan
Outputs are not used by the device unless the corresponding bit from the table below is enabled.
Table 4.28
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Reserved Reserved DO_ Relay_
Chan
DO_
ESD_Poll_
Cnxn
DO_
Position_
Chan
AO_ Ctrl_
Valve_
Flow_ Chan
4.2.13 DI_Alarms_2_Chan
Table 4.29
Bit 7 – Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Battery not installed
(only until first
time installed)
Flat battery indication Low battery
indication
Indication of
24VDC UPS
power available