Cut Sheet

Tray Cable Fittings
Silver Grip
®
TCF
®
Series —
Tray/Cord Fitting
HUB SIZE THROAT DIA. MIN. CABLE MAX. OPENING STD. PKG.
CAT. NO.
NPT (IN.) DIA. (IN.) (IN.) QTY.
TCF050-27AL
1
2 .330 .150 .270 25
TCF050-40AL
1
2 .540 .250 .400 25
TCF050-54AL
1
2 .540 .400 .540 25
TCF050-67AL
1
2 .540 .540 .670 10
TCF050-78AL
1
2 .540 .660 .780 10
TCF075-40AL
3
4 .540 .250 .400 15
TCF075-54AL
3
4 .540 .400 .540 15
TCF075-67AL
3
4 .780 .540 .670 10
TCF075-78AL
3
4 .780 .660 .780 10
TCF075-88AL
3
4 .765 .770 .880 10
TCF100-78AL 1 .980 .660 .780 10
TCF100-88AL 1 .980 .770 .880 10
TCF100-100AL 1 .980 .870 1.000 10
TCF125-109AL 1
1
4 1.255 .800 1.090 4
TCF125-128AL 1
1
4 1.255 1.080 1.280 4
TCF125-147AL 1
1
4 1.255 1.270 1.470 4
TCF150-115AL 1
1
2 1.470 .890 1.150 2
TCF150-140AL 1
1
2 1.470 1.140 1.400 2
TCF150-165AL 1
1
2 1.470 1.390 1.650 2
TCF200-153AL 2 1.896 1.190 1.530 2
TCF200-186AL 2 1.896 1.520 1.860 2
TCF200-219AL 2 1.896 1.850 2.190 2
TCF250-252AL 2
1
2 2.466 2.120 2.520 1
TCF300-278AL 3 2.780 2.380 2.780 1
TCF300-304AL 3 3.037 2.640 3.040 1
TCF300-330AL 3 3.068 2.900 3.300 1
For stainless steel (316), replace AL with SS6 (up to 1" only)
Introducing the Silver Grip
®
Tray/Cord Fitting — the safe, yet cost-efficient
choice for increased safety when terminating portable cord and tray cable in
hazardous locations. Designed for use in Class I, Gas and Vapor environments,
the Silver Grip
®
Tray/Cord Fitting provides efficient strain relief for cables
entering enclosures and raceways, and for cords used on portable equipment.
Now available in stainless steel in hub sizes from
1
2" to 1"
Corrosion-resistant, non-magnetic aluminum construction
Tapered neoprene bushing and O-ring seal out moisture
and dirt ingress
Chuck grip provides high mechanical pull-out performance.
Exceeds applicable requirements
Hand-tightens — no tools required
*When cord will not fit through body, strip
cord jacket and trim fillers if required. Insert
cable, ensuring the outer jacket reaches the
end of the bushing as shown. Tighten gland
nut onto body.
Maximum
Opening
Gland
Nut
Chuck
Grip
Bushing
Body
O-Ring
Increase safety for hazardous locations.
Silver Grip
®
TCF
®
Series —
Tray/Cord Fitting
Applications
Tray Cable: Complies with IEC requirements for Class I, Zone 2
locations when used with enclosures containing no arcing or sparking
devices. For enclosures with arcing or sparking devices, TCF
®
fittings
must be used in combination with a certified Class I hazardous
location sealing fitting.
Portable Cord: Complies with IEC requirements for Class I, Zone 1
locations when used with enclosures containing no arcing or sparking
devices. For enclosures with arcing or sparking devices, TCF
®
fittings
must be used in combination with a certified Class I hazardous
location sealing fitting.
NOTE: Tray cable is not suitable for use in Zone 1 locations. Portable
cord can be used in Zone 1 applications only when installed on
portable equipment.
CSA File Number LR4484
Class 4418-03 Fittings for Hazardous Locations
Class 4418-03 Fittings for Hazardous Locations —
Certified to U.S. Standards
Class I, Zone 1, AEx e ll
A-98
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
www.tnb.com
Now Available
in Stainless
up to 1"
Now Available
in Stainless
up to 1"