Cut Sheet
Table Of Contents
- T&B Fitting
- Product Overview
- Rigid & Intermediate Metal Conduit Fittings
- Form 7, Form 8, Series 35, Conduit Outlet Bodies & Covers
- Mogul Conduit Outlet Bodies
- FS/FD Cast Device Boxes and Covers
- Conduit Outlet Boxes
- Conduit Outlet Elbows, Reducers, Plugs, and Adapters
- Three-Piece Couplings
- Sealing Fittings
- Kopr-Shield Compound
- Jacketed Metal Clad Cable Termination Fittings
- Tray Cable Fittings
- EMT Fittings
- Liquidtight Flexible Metal Conduit Fittings
- Shureflex™ Nylon Conduit System
- XTRA FLEX System
- Flexible Cord and Cable Fittings
- Flexible Cord and Cable Fittings - Non-Metallic
- Service Entrance Cable Fittings
- Metal Clad Cable, Armored Cable and FlexibleMetal Conduit Fittings
- Non-Metallic Sheathed Cable Fittings
- Conduit Dimensional Data
Jacketed Metal Clad Cable Termination Fittings
STAR TECK EXTREME
®
Jacketed Metal-Clad Cable Fittings
DIMENSIONS (IN.) SEALING COMPOUND
HUB STRIP GLAND CABLE RANGE CABLE RANGE A1: THROAT A2: THROAT B C REQUIRED
CAT.
SIZE LENGTH TORQUE OVER JACKET (IN.) OVER ARMOR (IN.) DIA. MIN. DIA. MIN. OVERALL MAX. SC65 SC4-KIT
NO.
NPT (IN.) (IN.-LB.) MIN. MAX. MIN. MAX. W/END STOP WO/END STOP O.D. PUTTY (G) LIQUID (CC)
Ordinary Locations
ST050-462#
1
⁄2 1
1
⁄4 300 .525 .650 .415 .570 N/A* .395 2.020 1.224 — —
STE050DATA
**#
1
⁄2
7
⁄8 300 .592 .693 .502 .603 .375 .515 2.100 1.360 — —
STE050*
1
⁄2 1
1
⁄4 300 .600 .985 .520 .895 .505 .612 2.650 1.630 — —
STE075*
3
⁄4 1
1
⁄4 600 .860 1.205 .780 1.125 .655 .816 2.900 2.080 — —
STE100*11
1
⁄4 700 .950 1.375 .870 1.295 .785 1.044 3.020 2.300 — —
STE125*1
1
⁄4 1
1
⁄4 1,000 1.150 1.625 .990 1.465 .970 1.250 4.010 2.820 — —
STE150*1
1
⁄2 1
3
⁄4 1,200 1.440 1.965 1.280 1.805 1.260 1.562 4.290 3.250 — —
STE200*21
3
⁄4 1,600 1.825 2.375 1.665 2.215 1.645 1.995 4.120 3.600 — —
STE250 2
1
⁄2 2
1
⁄2 1,600 2.265 2.840 2.105 2.680 2.075 2.424 5.320 4.750 — —
STE300 32
1
⁄2 1,600 2.670 3.270 2.545 3.145 2.531 2.890 5.400 5.400 — —
STE350 3
1
⁄2 2
1
⁄2 1,600 3.220 3.870 3.090 3.640 3.065 3.460 5.360 5.900 — —
STE400 42
1
⁄2 1,600 3.665 4.340 3.550 4.225 3.525 3.941 5.415 6.400 — —
Hazardous Locations
STX050-462*
1
⁄2 1
1
⁄4 300 .525 .650 .415 .570 N/A* .395 2.500 1.630 7 4
STX050-464*
1
⁄2 1
1
⁄4 300 .600 .760 .490 .680 N/A* .485 2.530 1.630 7 4
STEX075*
3
⁄4 1
1
⁄4 600 .600 .985 .520 .895 .504 .678 3.400 1.820 14 7
STEX100*1 1
1
⁄4 700 .860 1.205 .780 1.125 .650 .833 3.580 2.300 30 16
STEX125*1
1
⁄4 1
1
⁄4 1,000 .950 1.375 .870 1.295 .834 1.065 3.920 2.510 45 22
STEX150*1
1
⁄2 1
3
⁄4 1,200 1.150 1.625 .990 1.465 .958 1.273 5.020 3.260 80 43
STEX200*2 1
3
⁄4 1,600 1.440 1.965 1.280 1.805 1.250 1.560 5.120 3.620 125 66
STEX250 2
1
⁄2 2
1
⁄2 1,600 1.825 2.375 1.665 2.215 1.640 1.995 5.170 4.580 341 164
STEX300 32
1
⁄2 1,600 2.265 2.840 2.105 2.680 2.075 2.461 6.610 5.100 497 239
STEX350 3
1
⁄2 2
1
⁄2 1,600 2.670 3.270 2.545 3.145 2.531 2.864 7.380 5.790 965 464
STEX400 42
1
⁄2 1,600 3.220 3.870 3.090 3.640 3.055 3.461 7.650 6.190 1323 636
STX400-484# 4 — 1,600 3.810 4.030 3.680 3.870 — — — — 1645 791
STX400-485# 4 — 1,600 3.965 4.185 3.835 4.025 — — — — 1645 791
STE Series Ordinary
STEX Series Hazardous Locations
Sealing Compounds — Used for Hazardous Locations
CAT. NO
. DESCRIPTION VOLUME
SC65 Putty Type Sealing Compound 60 grams
SC4-KIT Liquid Type Sealing Compound for use in high wire density applications 2.8 fl. oz. (66 cc)
(5 or more wires)
To specify other material, add the appropriate suffix to the category number.
DESIRED MATERIAL SUFFIX EXAMPLE
Aluminum fitting with grounding lock nut GRL STE-050GRL
Steel with zinc plate S STE-050S
Aluminum with PVC coating PVC STE-050PVC
Steel with PVC coating S-PVC STE-050S-PVC
*
These products are UL Listed Watertight NEMA Type 6P
** UL tested for data cables
# Does not have a removable armor stop.
A-91
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
www.tnb.com