Cut Sheet
Table Of Contents
- T&B Fitting
- Product Overview
- Rigid & Intermediate Metal Conduit Fittings
- Form 7, Form 8, Series 35, Conduit Outlet Bodies & Covers
- Mogul Conduit Outlet Bodies
- FS/FD Cast Device Boxes and Covers
- Conduit Outlet Boxes
- Conduit Outlet Elbows, Reducers, Plugs, and Adapters
- Three-Piece Couplings
- Sealing Fittings
- Kopr-Shield Compound
- Jacketed Metal Clad Cable Termination Fittings
- Tray Cable Fittings
- EMT Fittings
- Liquidtight Flexible Metal Conduit Fittings
- Shureflex™ Nylon Conduit System
- XTRA FLEX System
- Flexible Cord and Cable Fittings
- Flexible Cord and Cable Fittings - Non-Metallic
- Service Entrance Cable Fittings
- Metal Clad Cable, Armored Cable and FlexibleMetal Conduit Fittings
- Non-Metallic Sheathed Cable Fittings
- Conduit Dimensional Data
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof
Application
• Limits flames and/or explosions to area within electrical
system where they originate
• Limits pressure piling
• Required by NEC for conduit systems in hazardous
locations 18" from an enclosure housing a heat
producing or arcing device; on 2" and larger system
that enters an enclosure containing splices; wherever
conduit leaves a Class I, Division I area and enters
a non-hazardous area
Features
• Copper-free* aluminum provides increased
corrosion resistance
• Precision cast and machined surfaces permit
safer wire pulling
• Precision NPT threaded hubs enable trouble-free
field installation for rigid or IMC conduit
• Large opening provides maximum working room for
creating dam and seal pouring to speed up installation
• Compact design permits close construction
of parallel conduit runs
Standard Materials
• Sealing Fittings: Die cast aluminum alloy A360
with less than .004 copper content (copper-free)
• Sealing Cement
• Fiber: Flame retardant Kaowool Type A fiber
Standard Finish
• Aluminum lacquer finish
Listings/Compliances
• UL Listed
• CSA Certified
• Suitable for hazardous locations
• Federal Spec W-C-586
• CI.I, Div. 1 & 2, Groups C, D
CI.II, Div. 1, Groups E, F, G
CI.III, Div. 1 & 2
• NEMA 3, 4, 7 CD, 9 EFG
• Explosion-Proof
• Dust Ignition-Proof
• Raintight
• Wet Locations
Sample Specifications
• Sealing fittings for hazardous locations shall be die
cast copper — free* aluminum alloy A360. Suitable
for use in hazardous locations: Class I, Groups C, D;
Class II, Groups E, F, G and Class III. All conduit stops
shall be coined and free of rough edges. Sealing
fittings for hazardous locations shall be finished
with aluminum lacquer. Sealing fittings shall be
Thomas & Betts Catalog No. __________
*Less than .004% copper content.
Precision
machined
threads
Large
aperture
for easy
installation
Copper-free
aluminum
Smooth
conduit
stops
Vertical
HUB UNIT STD. WT. LBS.
CAT. NO. SIZE QTY. PKG. PER 100
† EYVF-1
1
⁄2" 5 25 50
† EYVF-2
3
⁄4" 5 25 54
† EYVF-3 1" 5 25 100
EYVF-11
1
⁄2"105035
EYVF-22
3
⁄4"105040
EYVF-33 1" 4 20 60
Vertical/Horizontal
HUB UNIT STD. WT. LBS.
CAT. NO. SIZE QTY. PKG. PER 100
EVHF-1
1
⁄2"105041
EVHF-2
3
⁄4" 5 25 50
EVHF-3 1" 5 25 60
EVHF-4 1
1
⁄4" 4 20 70
EVHF-5 1
1
⁄2"1 560
EVHF-6 2" 1 1 125
• EVHF-7 2
1
⁄2" 1 1 150
• EVHF-9 3
1
⁄2" 1 1 300
• Made to order items. Consult factory for lead time and minimum quantities.
† Packaged with an adequate amount of sealing compound
and plugs installed.