Cut Sheet
Table Of Contents
- T&B Fitting
- Product Overview
- Rigid & Intermediate Metal Conduit Fittings
- Form 7, Form 8, Series 35, Conduit Outlet Bodies & Covers
- Mogul Conduit Outlet Bodies
- FS/FD Cast Device Boxes and Covers
- Conduit Outlet Boxes
- Conduit Outlet Elbows, Reducers, Plugs, and Adapters
- Three-Piece Couplings
- Sealing Fittings
- Kopr-Shield Compound
- Jacketed Metal Clad Cable Termination Fittings
- Tray Cable Fittings
- EMT Fittings
- Liquidtight Flexible Metal Conduit Fittings
- Shureflex™ Nylon Conduit System
- XTRA FLEX System
- Flexible Cord and Cable Fittings
- Flexible Cord and Cable Fittings - Non-Metallic
- Service Entrance Cable Fittings
- Metal Clad Cable, Armored Cable and FlexibleMetal Conduit Fittings
- Non-Metallic Sheathed Cable Fittings
- Conduit Dimensional Data
Sealing Fittings Explosion-Proof, Dust-Ignition-Proof
Cl. I, Div. 1 & 2, Groups A, B, C, D
Cl. II, Div. 1, Groups E, F, G
Cl. III, Div. 1 & 2
EYD Drain Seals
HUB DIMENSIONS (IN.) TURNING
CAT. NO.
SIZE A B RADIUS
EYD11-TB
1
⁄2" 3.81 1.50 1.75
EYD21-TB
3
⁄4" 4.08 1.75 1.98
EYD31-TB 1" 4.85 2.19 2.19
EYD41-TB 1
1
⁄4" 5.00 2.25 1.80
EYD51-TB 1
1
⁄2" 5.44 2.44 2.00
EYD61-TB 2" 6.25 3.00 2.32
EYD71-TB 2
1
⁄2" 7.50 3.50 2.69
EYD81-TB 3" 8.50 4.25 3.15
EYD91-TB 3
1
⁄2" 9.19 4.75 3.38
EYD101-TB 4" 9.75 5.25 3.64
B
EYD
1
⁄
2
" — 1" EYD 1
1
⁄
4
" — 4"
EYD
1
⁄
2
" — 1"
Drains/Breathers for Hazardous Locations
HUB DIMENSIONS (IN.)
CAT. NO.
SIZE B
ECD15
1
⁄2" .975
ECD384
3
⁄8" .407
ECD284
1
⁄4" .327
Application
The Thomas & Betts Universal drain/breather fittings can be used as drains or breathers depending
on the installation.
• To use as a drain, the product must be installed in the bottom of the enclosure or the
lowest point where an NPT threaded opening exists. It can also be used in a seal fitting or
a “T” conduit body. These must be in a lower section of the conduit system. This will enable
moisture inside the conduit system to drain out
• To use as a breather, installation should be done at the top of an enclosure or in upper
sections of conduit systems. This will permit air exchange and keep moisture accumulation
inside the conduit system to a minimum, Thomas & Betts recommends the use of at least
2 devices (one drain and one breather) for maximum efficency
A-82