Cut Sheet

Conduit Outlet Bodies
Explosion-Proof, Dust-Ignition-Proof
OE Series — Iron Conduit Outlet Bodies
HUB DIMENSIONS (IN.)
CAT. NO.
SIZE A B C D E F
OEC1-TB
1
2" 4.06 1.62 1.90 0.69 0.88 0.63
OEC2-TB
3
4" 4.35 1.88 2.19 0.69 0.88 0.76
OET1-TB
1
2" 4.06 1.62 1.90 0.69 0.88 0.63
OET2-TB
3
4" 4.35 1.88 2.19 0.69 0.88 0.76
OELL1-TB
1
2" 4.06 1.62 1.90 0.69 0.88 0.63
OELL2-TB
3
4" 4.35 1.88 2.19 0.69 0.88 0.76
OELR1-TB
1
2" 4.06 1.62 1.90 0.69 0.88 0.63
OELR2-TB
3
4" 4.35 1.88 2.19 0.69 0.88 0.76
OELB1-TB
1
2" 4.06 1.62. 1.90 0.69 0.88 0.63
OELB2-TB
3
4" 4.35 1.88 2.19 0.69 0.88 0.76
Application
OE series are installed in conduit systems within hazardous areas to:
Protect conductors in threaded rigid conduit
Act as pulling and splice fittings
Interconnect lengths of conduit
Change direction of conduit
Provide access for maintenance and future system changes
Features
OE conduit bodies have:
Tapered threaded hubs for ground continuity
Smooth integral hub bushings to protect conductor insulation when pulling
Five different hub arrangements
Accurately machined body with blind tapped screw holes
Most compact design of all hazardous area outlet bodies
Sizes up to 1"
Standard Materials
Bodies: Grade 60-45-10 Ductile Iron (Complies with ASTM standard A536)
Standard Finish
Electrogalvanized and aluminum acrylic paint
Size Ranges
Hub —
1
2" and
3
4"
Listings/Compliances
CI.I, Div. 1 & 2, Groups C, D
CI.II, Div. 1, Groups E, F, G
CI.III, Div. 1 & 2
NEMA 3, 4, 7 CD, 9 EFG
Explosion-Proof
Dust-Ignition-Proof
Raintight
Wet Locations
A-76
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
www.tnb.com