Installation Manual
MAIN
L
TAP
H
Figure 2 - Requires 3 crimps
Figure 1
45H 45H
Ground Rod
Pre-Crimped (15526 Die)
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA02145 D
Page 1 of 1
© 2015 Thomas & Betts. All Rights Reserved.
WARRANTY:
Thomas & Betts sells this product with the understanding that the user will perform all necessary
tests to determine the suitability of this product for the user's intended application. Thomas & Betts warrants
that this product will be free from defects in materials or workmanship for a period of two (2) years following
the date of purchase. Upon prompt notification of any warranted defect, Thomas & Betts will, at its option,
repair or replace the defective product. Misuse, misapplication or modification of Thomas & Betts Products
immediately voids all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU
OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH
OF THE ABOVE WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO
CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
CATALOG
NUMBER
APPLICATION CABLE TO REBAR APPLICATION
DIES FOR
T&B TOOLS
(see Step 4)
L
MAIN TAP MAIN TAP
54900 250 MCM-500 MCM OR 5/8” - 3/4” ROD 350 MCM-500 MCM #5 REBAR 5/8” THRU 3/4” #6 REBAR 350 MCM-500 MCM 15G121R* 1-1/8”
54895 250 MCM-500 MCM OR 5/8” - 3/4” ROD 3/0 STR-250 MCM #5 REBAR 5/8” THRU 3/4” #6 REBAR 3/0 STR - 250 MCM 15G126R 3/4”
54890 250 MCM-500 MCM OR 5/8” - 3/4” ROD 1/0 STR-2/0 STR #5 REBAR 5/8” THRU 3/4” #6 REBAR 1/0 STR - 2/0 STR 15G126R 3/4”
54885 250 MCM-500 MCM OR 5/8” - 3/4” ROD #4 SOL-#2 STR 15G126R 3/4”
54875 #6 SOL - #2 STR #6 SOL-#2 STR 15501A 3/4”
54865 1/0 STR-250 MCM OR 1/2” - 5/8” ROD 3/0 STR-250 MCM #3 REBAR 3/8” THRU 1/2” #4 REBAR 3/0 STR - 250 MCM 15G86R 3/4”
54860 1/0 STR-250 MCM OR 1/2” - 5/8” ROD 1/0 STR-2/0 STR #3 REBAR 3/8” THRU 1/2” #4 REBAR 1/0 STR - 2/0 STR 15G86R 3/4”
54855 1/0 STR-250 MCM OR 1/2” - 5/8” ROD #4 SOL-#2 STR #3 REBAR 3/8” THRU 1/2” #4 REBAR #2 STR 15G86R 3/4”
54865-CKN 5/8” ROD (Fig. 1) 3/0 STR-250 MCM 15506 (Fig. 2) 1-1/2”
54860N 5/8” ROD 1/0 STR-2/0 STR 15506 (Fig. 2) 1-1/2”
54855N 5/8” ROD #4 SOL-#2 STR 15506 (Fig. 2) 1-1/2”
54875N #6 SOL - #2 STR #6 SOL-#2 STR 15517 (Fig. 2) 1-1/2”
INSTRUCTIONS:
NOTE: INSTALL THESE CONNECTORS ON
GROUND RODS AFTER THE RODS HAVE
BEEN DRIVEN TO THEIR FINAL DEPTH.
1. Clean cable of all visible dirt with rough cloth or
brush and provide a bright copper nish by wire
brushing or similar process.
2. Optional: Use knurling tool 240-31565-94 on
smooth ground rods.
3. Cable end(s) should protrude at least 3/4” beyond
connector.
4. Use hydraulic tool 13100A, TBM14M
TBM14CR-LI, TBM15CR-LI, TBM15, or TBM15I
with die indicated in chart.
IMPORTANT:
For 54865-CKN Only. To be in compliance
with IEEE837-2014, the ground rod should be
pre-crimped with die 15526 (45H) as shown in Figure 1.
INSTRUCTION SHEET
For Ground Grid Connector
CATALOG
NUMBER
H L
DIES FOR
Y750/Y35/Y39
DIES FOR Y45 DIES FOR Y46
NUMBER
OF CRIMPS
54900 2-7 /16” 1-1/8” U1011 S1011 P1011 3
54895 2-3/16” 3/4” PU998 PU998 OR S998 PU998 OR S998 1
54890 2-1/8” 3/4” PU998 PU998 OR S998 PU998 OR S998 1
54885 1-15/16” 3/4” PU998 PU998 OR S998 PU998 OR S998 1
54875 2-9/16” 3/4” UO UO UO 1
54865 2-3/16” 3/4” 997 U997 U997 1
54860 1-31/32” 3/4” 997 U997 U997 1
54855 1-15/16” 3/4” 997 U997 U997 1