Installation Guide

Rev.1.12.09.10 8
Installation Methods:
Ceramic & Porcelain Tile Method #3-1: Ceramic floor tile (8” or larger) on concrete sub-floor
Setting Materials:
Use Latex Portland cement mortar that conforms to test
requirements found in ANSI A118.4.
• Hydrate (mix with water) according to the bag recommendations.
• Use a slow mixer (300 rpm or less) or mix by hand.
• Allow mixture to sit undisturbed for 15 minutes, then lightly remix.
Trowel Size:
WarmFlex to sub-floor: 1/4”x1/4”x1/4” Square or “U” notch.
Tile to WarmFlex: Use a square or “U” notch trowel with notch size
appropriate for the size and type of tile installed. Minimum 1/4”x3/8”x1/4”.
Concrete Requirements:
• Maximum variation of 1/4” in 10’-0”. Deflection is not to exceed 1/360 of span.
• All cracks in excess of 1/16” must be filled as per ANSI specifications.
• Surface must be clean, dry and free of contaminants and sealers.
• Lightweight concrete surfaces must comply with manufacturer’s specifications for tile installations.
Installing WarmFlex
1. Lay out the WarmFlex .
2. Leave approximately 3” of space between the walls and WarmFlex to run lead wires.
3. Pull back the WarmFlex.
4. Dampen, but do not saturate, the concrete floor with a sponge or a mist sprayer.
5. Key the thin-set mortar into the sub-floor with the flat side of a 1/4”x1/4” square or “U” notch trowel and then comb it
with the notched side using a left to right motion.
6. Apply the thin-set mortar only as far ahead as will allow installation of the WarmFlex
®
prior to the mortar beginning to
set or “skin over”.
7. Lay the WarmFlex and lead wires back into the thin-set.
8. Immediately (within 10 minutes) roll the WarmFlex with a 75lb roller in diagonal directions.
9. Do not walk on the rolled areas. Allowing traffic on the installed WarmFlex prior to full set may cause indentations
resulting in weak areas and hollow spots.
10. Make sure no trowel notch ridges remain under the WarmFlex.
11. Seams should be butted together, leaving no gaps or overlaps.
12. Allow the WarmFlex to set for at least 16 hrs.
Ceramic and Porcelain Tile Method #3-2: Tile on Plywood Sub-floor
Setting Materials:
• For WarmFlex to sub-floor: use EGP (Exterior Glue Plywood)
Latex Portland Cement Mortar that conforms to ANSI A118.11.
• For Tile to WarmFlex: use Latex Portland Cement Mortar that
conforms to ANSI A118.4.
Trowel Size:
WarmFlex mat to sub-floor: 1/4” x 1/4” x 1/4” Square or “U” notch.
• Tile to WarmFlex: Use a square or “U” notch trowel with notch size
appropriate for the size and type of tile installed. Minimum 1/4”x3/8”x1/4”.
Sub-Floor Requirements:
• Sub-floor assembly must comply with ANSI A108.12.
• 16”oc, 2”x10” minimum joist: total sub-floor thickness -1 1/8” with clean structurally sound exterior plywood as
the top surface.
• 24”oc truss or I-joist: total sub-floor thickness - 1 1/2” with clean structurally sound exterior plywood as the
top surface.
• Must be free of all sealers and contaminants.
• Maximum variation of 1/8” in 10’-0”.
• Deflection is not to exceed 1/360 of span when measured under 300lb concentrated load (see ASTM C627).
Installing WarmFlex
(Same as Installation Method #3-1)
3-2
WarmFlex
3-1
WarmFlex
Concrete Slab Subfloor
Plywood Subfloor