Owner's manual

CONTRACTOR
Page 25
drains. In order to eliminate the residues and keep the tank as clean as possible, the humidi er also drains
after a certain number of boiling – re ll cycles. If there is still a demand from the humidistat after draining, the
tank re lls and starts to produce steam again.
20.15 When the humidistat is satis ed, the fan continues to run for a short period of time in order to eliminate
the steam from the ducts.
20.16 When everything is working ne, put the cover on the unit and attach it by turning the 1/4 turn latch to
the right.
20.17
Please don’t forget to leave this instruction manual with the customer.
20.18 Sequence of Operation.
* The unit will repeat this cycle until the humidistat is satis ed or the selected number of cycles is reached
before going to the draining cycle. If there is no more demand for humidity, the unit will automatically go on
Stand By mode until the next demand. If there is no demand for 7 days, the unit will ush and drain the tank.
NOTE:
The Acu-Steam board has a memory that remembers the last sequence of operation when the power is turned
off, hence the unit might start at step 2 or 3 when you put the power back on. Also, timings may slightly vary
depending on the capacity of the unit (1.5 kW, 3 kW or 4 kW), the pressure of the water inlet and the quality of
the water.
Power
On
Filling
Cycle
12 3 45678
Draining Cycle Boiling Cycle
Up to 5 sec. Up to 3 min. Up to 4 min.
Up to 9 minutes total for drain cycle 1 Steam cycle* (see below)
Up to 2 min. Up to 2 min. Up to 5 sec. Up to 6 min. Up to 20 sec.
!