Instruction Manual

THERMO-V SPECIFICATION
Supply where indicated in these specifications, or where shown on drawings, CSA (NRTL/C) approved THERMO-V type
heaters specially designed for VAV boxes and manufactured by THERMOLEC.
1- AIR FLOW:
The proportional electronic air flow sensor shall be totally independent of the duct static pressure and shall adjust
the heater capacity according to the available air flow:
The heaters shall deliver maximum heating when needed with normal minimum air flow, reduce heating with lower
than minimum air flow and stop heating with no air flow.
2- CONTROL AND INPUT SIGNAL:
Heaters shall be equipped with a proportional controller to modulate the heater load according to the temperature
control signal.
The electronic controller shall be compatible with the following input signals:
- Variable voltage signal 0-10 VDC
- Pulse with modulation AC or DC
3- CONSTRUCTION:
Frame shall be corrosion-resistant and made of galvanized steel of suitable gauge as required by CSA.
Coils shall be made of high grade Nickel-Chrome alloy and shall be insulated by floating ceramic bushings from the
galvanized steel frame.
Coil terminal pins shall be in stainless steel, mechanically secured and insulated from the frame by means of non-
rotating ceramic bushing.
Coil support bushing shall be made of ceramic and shall be held in the frame by a lock which will keep it floating and
stress-free.
Heaters shall be CSA approved for zero clearance in horizontal ducts.
4- SAFETY AND BUILT-IN CONTROLS:
Heaters shall be equipped with fail-safe automatic reset disc thermal cut-out.
In addition, heaters of 30KW and less, rated for voltages below 300 volts shall be equipped with a fail-safe disc type
manual reset thermal cut-out as required by CSA.
Cut-outs shall de-energize the heater in case of accidental over-heating.
For maintenance and safety purposes, the heaters shall be equipped with a built-in disconnect to switch the power
off at the heater location and protective screens on both sides.
Load fuses shall be supplied as recommended by NEC (National Electrical Code).
All duct heaters shall be complete with the following built-in controls : magnetic contactors as required, control
transformer, proportional electronic controller and air flow sensor as standard components.
5- SIZE & CAPACITY:
Heater size, volts, phase, kilowatts shall be as per the following schedule.
6- INTERNAL WIRING:
All internal wiring shall terminate on clearly identified terminal blocks.
A wiring diagram shall be installed on the control box cover.
Prior to shipment, heaters shall withstand tests as required by CSA.
7- APPROVALS:
Heaters data sheets, wiring diagrams and mechanical drawings shall be submitted to the consulting engineer for
approval before manufacturing.
THERMO-V SPECIFICATION
THERMOLEC