Instruction Manual

TUBULAR HEATER SPECIFICATION
Long Form (continued)
6- INTERNAL WIRING:
All internal wiring shall terminate on clearly identified terminal blocks.
A wiring diagram shall be installed on the control box cover.
Prior to shipping, heaters shall withstand tests as required by CSA.
7- STANDARD BUILT-IN CONTROLS:
All duct heaters shall be complete with the following built-in controls:
High limit cut-outs, magnetic contactors as required, control transformer and air flow sensor as standard
components.
Additional options can be chosen from the following list:
Mercury contactors
Unfused disconnect switch
SCR proportional controller
HRC Form 1 load fuses
Hybrid controller with SCR and binary steps
Pressure Electric switches
Pneumatically controlled SCR
Pilot lights to indicate staging, control voltage on, power supply on, overheating, no air flow, heating on
8- SPECIAL CONSTRUCTION:
Heaters could be equipped with a bottom terminal box, weatherproof shroud or any other feature selected from the
option list (see section 2).
9- APPROVALS:
Heaters data sheets, wiring diagrams and mechanical drawings shall be submitted to the consulting engineer for
approval before manufacturing.
THERMOLEC