Instruction Manual

SPECIFICATION FOR TUBULAR HEATERS
Long Form
Supply where indicated in these specifications CSA (NRTL/C) approved tubular duct heaters as manufactured by
THERMOLEC.
1- CONSTRUCTION:
Frame shall be corrosion-resistant and made of galvanized steel of suitable gauge as required by CSA.
Heating elements shall be tubular type made of heavy gauge Incoloy 800 filled with compacted magnesium oxide
insulating powder.
Above 277 Volts or 30KW, each tube shall be of "U" type and shall be removable through the control box without
removing the heater from its ductwork.
2- SAFETY CONTROLS:
Heaters shall be equipped with fail-safe automatic reset disc-type thermal cut-out(s) located in the top frame
component above the heating elements.
In addition to the automatic reset cut-out, heaters of 30 KW and less, rated for voltages below 300 volts shall be
equipped with a fail-safe manual reset disc-type thermal cut-out, semi-recessed in the terminal box, facing the
heating element hairpin as required by CSA.
The sensing element of the cut-out shall be stream mounted, shall be shielded from mechanical damage and shall
face the center portion of the heating section so as to make the heater non-sensitive to air flow direction.
Cut-outs shall de-energize the heater in case of insufficient air flow.
For maintenance and safety purposes, a built-in disconnect shall be supplied to switch the power off at the heater
location.
Load fuses shall be supplied as required by NEC (National Electrical Code).
3- AIR FLOW:
Duct heaters shall be non-sensitive to air flow direction and interchangeable for horizontal or vertical ducts.
4- MOUNTING METHOD:
Heaters shall be ST slip-in type or model FT flanged type, as shown on the plans or on the heater schedule.
Slip-in heaters shall be suitable for insertion into the duct through an opening on its side and shall have a flange for
securing it to the duct side.
Flanged heaters shall be suitable for attaching to matching flanges on the duct.
Mounting flanges on both models shall be independent of the terminal box so as to allow installation without opening
the box or drilling into it.
5- SIZE & CAPACITY:
Heater size, volts, phase kilowatt and number of control stages shall be as per heater schedule.
TUBULAR HEATER SPECIFICATION