Instruction Manual

SPECIFICATION FOR OPEN COIL HEATERS
Long Form
Supply where indicated in these specifications, or where shown on drawings, CSA (NRTL/C) approved open
coil duct heaters as manufactured by THERMOLEC.
1- CONSTRUCTION:
Frame shall be corrosion-resistant and made of galvanized steel of suitable gauge as required by CSA.
Coils shall be made of high grade Nickel-Chrome alloy and shall be insulated by floating ceramic bushings from the
galvanized steel frame.
Coil terminal pins shall be in stainless steel, mechanically secured and insulated from the frame by means of
non-rotating ceramic bushing.
Coil support bushing shall be made of ceramic and shall be held in the frame by a lock which will keep it floating and
stress-free.
2- SAFETY CONTROLS:
Heaters shall be equipped with fail-safe automatic reset disc-type thermal cut-out(s) located in the top frame
component above the heating elements.
In addition to the automatic reset cut-out, heaters of 30KW and less, rated for voltages below 300 volts shall be
equipped with a fail-safe manual reset disc-type thermal cut-out, semi-recessed in the terminal box, facing the
heating element hairpin as required by CSA.
The sensing element of the cut-out shall be stream mounted, shall be shielded from mechanical damage and shall
face the center portion of the heating section so as to make the heater non-sensitive to air flow direction.
Cut-outs shall de-energize the heater in case of insufficient air flow.
For maintenance and safety purposes, the heater shall be equipped with a built-in disconnect to switch the power
off at the heater location (option X1) and protective screens on both sides (option MS).
Load fuses shall be supplied as recommended by NEC (National Electrical Code).
When heaters are used in VAV systems, they should be modulating type “THERMO-V” equipped with an electronic
air flow sensor as described in item #8.
3- AIR FLOW:
Duct heaters shall be non-sensitive to air flow direction and interchangeable for horizontal or vertical ducts without
impairing safety.
Heaters shall be CSA approved for zero clearance in horizontal ducts.
4- MOUNTING METHOD:
Heaters shall be open coil model SC slip-in type or model FC flanged type, as shown on the plans or on the coil
schedule.
Slip-in heaters shall be suitable for insertion into the duct through an opening on its side and shall have a flange for
securing it to the duct side.
Flanged heaters shall be suitable for attaching to matching flanges on the duct.
Mounting flanges on both models shall be independent of the terminal box so as to allow installation without opening
the box or drilling into it.
5- SIZE & CAPACITY:
Heater size, volts, phases, kilowatt and number of control stages shall be as per heater schedule.
6- INTERNAL WIRING:
All internal wiring shall terminate on clearly identified terminal blocks.
A wiring diagram shall be installed on the control box cover.
Prior to shipping, heaters shall withstand tests as required by CSA.