User Manual

Page 31
CONTRACTOR
Number of ashes
of the red light
Error Description Humidi er Status
Actions to be Taken
by the Technician
Reset
OFF
No error The humidi er is working ne None
Countinuous
ON
The ood sensor under the tank
senses water in the pan.
Humidi er immediately suspends the
ongoing operation. Heating elements and
supply valve are switched off. The power
green light is blinking.
Turn power off. Check for leaks around the
tank clamp, SW valve and drain tube. Make
sure tank arrows align and gasket is sealing
properly.
Automatic Reset when
Over ow pan dries up.
1
The two water level sensors are
miswired or do not read the water
level properly.
Humidi er attempts to operate, then stops
because of wrong information from water
level sensors. The power green light is
blinking.
Turn power off. Clean or replace HLS or LLS
water sensors. Check for proper wiring of
HLS and LLS sensors.
Automatic Reset when
switching main power ON
3
Inadequate water supply. The
supply valve was open for more
than 6 minutes.
Humidi er immediately suspends the ongo-
ing operation. Heating elements and supply
valve are switched off. The power green
light is blinking.
Turn power off. Check SW valve circuit for
24V DC at the valve. Refer to manual (p. 20)
and check for proper drain installation. Make
sure SW shut-off valve is open, SW valve is
responding and SW tube is clear of debris.
Automatic Reset after
5 min or when switching
main power off and on
4
Inadequate drainage. The tank
did not drain or the draining cycle
is too long.
Humidi er immediately suspends the
ongoing operation. Heating elements and
supply valve are switched off. The power
green light is blinking.
Turn power off. Check for proper drain setup
by referring to manual (p. 20). Check and
clean tank, SS siphon tube and silicon drain
tube if necessary.
Automatic Reset when
switching main power ON
5
The air pressure switch does not
detect enough air pressure OR
the high limit HSTAT (optional)
senses extremely high humidity
in the duct.
Humidi er immediately suspends the
ongoing operation. The unit goes back
to normal operation as soon as the error
condition disappears. The power green light
is blinking.
Check if the FF motor is running. If not, turn
FF to continuous operation. Check ow sensor
(pitot tube) in duct for blockage, then make
sure plastic tube is connected properly from
ow sensor to PD switch under PC board in
unit (see manual). Change furnace lter if
needed.
Automatic Reset
when error conditions
disappear
6
Temperature inside the tank
exceeded the high temperature
cut-out setting.
The high temperature cut-out has tripped.
The humidi er immediately suspends the
ongoing operation. Heating elements and
supply valve are switched off. The power
green light is blinking.
Turn power off. This is a serious condition and
will likely require assistance from a service
technician. Call 1-800-336-9130.
After pushing on the
thermal cut-out button,
automatic reset when
switching main power ON
22. Detailed Error Codes
Legend: SS = stainless steel, FF = furnace fan, SW = supply water, HLS = high level sensor, LLS = low level sensor