User Manual

Page 26
CONTRACTOR
20. Start-up and Test Procedure
20.1 Turn the breaker “ON” to supply power to the humidi er. The green light comes ON to con rm that the
unit is ready to work.
20.2 Test of the On/Standby button. Press the white button once. The green light goes OFF then ashes,
indicating that the unit is in standby mode but still powered. Press the white button again and keep it depressed
for 3 seconds to power the humidi er. The green light will come ON, con rming that the unit is ready to work.
20.3 Turn the humidistat clockwise past the middle of the scale to create a demand for humidity.
20.4 The tank lls to the proper water level.
20.5 The fan control starts the fan to move the air as the humidi er starts boiling water and produces steam.
If the fan cannot start, the humidi er suspends the ongoing operation. If the air pressure is insuf cient, the unit
will stop by itself. Please note that it may take a few minutes to bring the water to a boil. The steam exits the
water tank through the steam outlet and steam hose.
20.6 The steam moves through the hose to the diffuser and is released into the warm air duct where it mixes
with the moving air.
20.7 As water evaporates in the tank, the electric valve opens as needed to maintain the proper water level.
20.8 When the humidity reaches the desired level the humidi er stops producing steam. In order to eliminate
the residues and keep the tank as clean as possible, the humidi er drains after a certain number of boiling –
re ll cycles. If there is still a demand from the humidistat after draining, the tank re lls and starts to produce
steam again.
20.9 When the humidistat is satis ed, the fan continues to run for a short period of time in order to eliminate
the steam from the ducts.
20.10 When everything is working ne, put both covers back on the unit and attach them with the two screws
(electrical cover) and by turning the 1/4 turn latch to the right (tank cover).
20.11 Sequence of Operation.
* The unit will repeat this cycle until the humidistat is satis ed or the selected number of cycles is reached
before going to the draining cycle. If there is no more demand for humidity, the unit will automatically go on
ready mode until the next demand. If there is no demand for 7 days, the unit will ush and drain the tank.
Power
On
Filling
Cycle
12 3 45678
Draining Cycle Boiling Cycle
Up to 5 sec. Up to 3 min. Up to 4 min.
Up to 9 minutes total for drain cycle 1 Steam cycle* (see below)
Up to 2 min. Up to 2 min. Up to 5 sec. Up to 12 min. Up to 20 sec.
!